WARNING:

These fire protection devices require correct wiring to function. It is the responsibility of the purchaser to provide 
qualified correct wiring installation. SARGENT accepts no responsibility for incorrect wiring. Devices wired 
incorrectly may be damaged and this is not covered under warranty.

Life safety devices require correct positioning and appropriate selection for the required task.  It is the responsibility 
of the purchaser to select appropriate hardware and provide professional installation.  It is the responsibility of the 
purchaser to insure that NFPA and other applicable fire codes are met.  Door release devices function properly only if 
the door is free to close and is installed correctly. SARGENT accepts no responsibility for incorrect installation of its 
equipment.

Smoke detectors will not work without power.  AC or DC powered smoke detectors will not work if the power supply 
is cut off for any reason.

All high voltage wiring should be undertaken by a qualified professional licensed electrician.  It is the responsibility 
of the purchaser to insure that installation meets all applicable local and national electrical codes.

A detector may not detect a fire developing on another level of a building.  For this reason, detectors should be 
located on every level of the building.

Smoke detectors will not sense fires which start where smoke does not reach the detectors.  Smoke from fires in 
chimneys, in walls, on roofs, or on the other side of a closed door may not reach the smoke detector and activate it.

Smoke detectors cannot last forever.  Smoke detectors contain electronic parts.  Even though detectors are made to 
last over 10 years, any of these parts could fail at any time.  Therefore, test your smoke detector system per NFPA 72 
Chapter 10 at least semiannually.  Clean and take care of your smoke detectors regularly.  Refer to Page 5 of these 
instructions for “Smoke Detector Cleaning and Testing”.  Taking care of the fire detection system you have installed 
will maintain the reliability of the system. 

Smoke detectors have sensing limitations.  Photoelectric detectors sense smoldering fires better than flaming fires. 
Ionization detectors offer a broad range of fire-sensing capability, but they are better at detecting fast, flaming fires 
than slow smoldering fires. Because fires develop in different ways, and are often unpredictable in their growth, 
neither type of detector is always best, and a given detector may not always provide warning of a fire. In general, 
detectors cannot be expected to provide warning for fires resulting from inadequate fire protection practices, violent 
explosions, escaping gas, improper storage of flammable liquids like cleaning solvents, other safety hazards, or 
arson. Smoke detectors used in high air velocity conditions may fail to alarm due to dilution of smoke densities 
created by such frequent and rapid air exchanges.  Additionally, high air velocity environments may create increased 
dust contamination, demanding more frequent maintenance.

!

120VAC “12-2409” Master Unit shown

120VAC “2409” Support Unit shown

Opening for 

Surface Wiring

Test Switch

Test Switch

Red LED / Reset Switch

Smoke Detector

Solenoid Connection

Circuit Board

Solenoid Connection

Jumper

Opening for 

Concealed Wiring

Power Input

Jumper

Circuit Board

Power Inputs

2

Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group 
company, All rights reserved. Reproduction in whole or in part without the 
express written permission of Sargent Manufacturing Company is prohibited.

A8200 (10/15)

Содержание Sargent 2409 Series

Страница 1: ...hru 8 of these instructions 24VDC 2409 Support Unit shown 12 2409 Master Unit shown Hinge Edge of Door Hinge Edge of Door Hinge Edge of Door INSTALLER LEAVE INSTRUCTIONS WITH BUILDING OWNER CAUTION 1...

Страница 2: ...s any of these parts could fail at any time Therefore test your smoke detector system per NFPA 72 Chapter 10 at least semiannually Clean and take care of your smoke detectors regularly Refer to Page 5...

Страница 3: ...elease their doors The unit that initiated the alarm will have its LED on The LED on the other interconnected units will flash as normal Refer to Interconnection Wiring Diagram for connections CONNECT...

Страница 4: ...h 4 pin jumper for non detectored units 120V AC INPUT CIRCUIT BOARD shown with Wiring Harness detectored units TWO PIN JUMPER WIRE SOLENOID CONNECTION WIRING HARNESS SEE PAGES 6 8 FOR ADDITIONAL WIRIN...

Страница 5: ...pen now Maintenance of Smoke Detectors It is recommended to clean smoke detectors at least every six months The frequency of cleaning will depend upon local ambient conditions The smoke detector in th...

Страница 6: ...VDC Solenoid Alarm Panel Alarm Circuit Trouble Circuit EOL Res 2 24VDC 0 15A Max To External Alarm 1 24V AC DC or 120V AC Input from Regulated Power Supply MPS10 or equiv 24V DC 0 15A Max To External...

Страница 7: ...or equiv Earth Ground 1 2 3 4 P1 P3 Circuit Board 2 1 3 Two Pin Jumper Wire 24VDC Solenoid 24V AC DC or 120V AC Input from Regulated Power Supply MPS10 or equiv Earth Ground 1 2 3 4 P1 P3 Circuit Boa...

Страница 8: ...2 3 5 4 Remote Detector Relay 4 15 10 4 4 4 15 15 15 C N O 8 Copyright 2015 Sargent Manufacturing Company an ASSA ABLOY Group company All rights reserved Reproduction in whole or in part without the e...

Отзывы: