Troubleshooting

Fault

Possible Reasons Why

Remedies/Explanations

The door does not open

- the motor does not start

Control switch is set to OFF position

Electrical power is missing

Activation unit does not function

Circuit breaker is set to OFF position

Reset the circuit breaker to the ON position

Jump activation input to verify

Check the electrical power switch

Change the setting of the ON/OFF switch

- the motor continues
  to run

Motor is driving in wrong direction

Something jammed beneath the door

Arm has come loose

Flip Door Mounting Dip Switch to other direction

Remove object

Re-install arm and key

The door does not close

Closing power set too low

Arm has come loose

The door is binding or obstructed

Control switch is set to OFF position

Re-install arm and key

Inspect hinges and frame for wear or obstruction

Change the setting of the ON/OFF switch

Adjust P1 or P2 according to instructions on pg. 7 

Maintenance (Service by Authorized Personnel Only):

Disconnect power before servicing.

Frequency of maintenance will depend on factors such as traffic, climate, etc.  To make sure your 
operator is working correctly you should periodically check wire connections, tightness of arm 
connection and screws, and wear and tear on hinges/pivots. 

No serviceable user parts!

The door opens and 
stays open when first
energized.

SW501 is set incorrectly

Change the switch setting to the correct handing. 
See instructions on page 5

The electric strike or
electromagnetic lock
does not work.

JMP503 is set incorrectly

Loose or shorted wire to strike or lock

See instructions on page 9 or 10

Inspect wires running from unit to latch device

Provide power to strike or electromagnetic lock from
another source. 

Power from unit insufficient for strike
or electromagnetic lock

Содержание Norton 5630 Series

Страница 1: ...e Screwdriver Phillips size 2 Tape ruler Power drill Center punch Wire stripper 7 drill 1 4 20 tap metal frame install Tools required Use screw pack and hardware provided to mount operator ETL certifi...

Страница 2: ...ates still active If desired overhead presence devices can be provided for an extra level of protection Consult local authority having jurisdiction These are not required by current ANSI BHMA A156 19...

Страница 3: ...butt hinges Maximum frame reveal is 4 for this application Before beginning the installation verify that the door frame is properly reinforced and is well anchored in the wall Unreinforced hollow met...

Страница 4: ...3 16 4x 15 16 2 2 1 2 6 5 8 4 3 4 4 1 8 1 2 Operator Mounting WARNING DO NOT REMOVE ARM FROM OPERATOR WARNING ARM MUST CLEAR FRAME SOFFIT 1 Left hand door illustrated 1 Using template locate and prepa...

Страница 5: ...agnets are used to signal the unit at closed and fully open positions With door in the closed position slide Close Position Magnet so it aligns directly with the sensor With door in the open position...

Страница 6: ...rminal Description HOT COM Common power lead Neutral Hot power lead 120VAC 60Hz Input Wiring Instructions Grounding 7 WARNING UNIT WILL NOT FUNCTION CORRECTLY WITHOUT PROPER GROUNDING GROUND WIRE MUST...

Страница 7: ...ion adjustment desired use table below to determine which POT is to be adjusted Required Magnets must be adjusted for specific application WARNING ELECTRIC SHOCK RISK Adjustments made in the shaded ar...

Страница 8: ...ly closed Activating either switch will open both doors Door will close after hold open time delay has elapsed Door 1 Optional Door 2 Wave to Open Switch Wiring Operation Door is normally closed Activ...

Страница 9: ...Radio Frequency Feature can be purchased as a separate kit and installed as pictured below Operation Door is normally closed Activating wireless switch or hand held wireless transmitter will open the...

Страница 10: ...Lock Fail Safe Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts 1 2 3 4 5 6 Signal input Signal common Relay output K2 Relay output K1 24 VDC 24 VDC 3 5 Jumper wire 22ga or...

Страница 11: ...2x 1 5 16 1 1 8 6 5 8 2 1 2 2 14 16 1 2 Hinge or Pivot 2x 1 3 16 4x 15 16 2x 1 4 20 Machine Screws or Self Drilling Screws See Page 3 Figure 1 Frame Soffit Frame Rabbet Hinge or Pivot 16 1 2 2x 1 3 1...

Страница 12: ...as come loose The door is binding or obstructed Control switch is set to OFF position Re install arm and key Inspect hinges and frame for wear or obstruction Change the setting of the ON OFF switch Ad...

Страница 13: ...le or in part without the express written permission of Yale Security Inc is prohibited ASSA ABLOY 80 9356 0005 020 01 14 13 For assistance contact Norton Technical Product Support at 877 974 2255 300...

Отзывы: