Copyright © 2013, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited.
ASSA ABLOY
80-9356-0005-020 (01-14)
10
Fail Safe Electromagnetic Lock 24VDC Wiring
Notes:
1. Power input to Door Operator Unit is at “T1” Power
Input Terminal (not shown) 120VAC 60Hz.
2. Unit’s Relay Rating: 30VDC @ 1A or 125VAC @ .5A
Operation:
Door is normally closed and latched.
Activating switch will cut power to mag lock and the door will automatically
open. Door will close after hold open time delay has elapsed.
The door will
unlock
during power failure.
Jumper Settings
Place jumper to upper position
for normally closed operation.
JMP503
NC
NO
24VDC Electromagnetic Lock
(Fail Safe)
+
-
Wall Switch, Card Reader,
Key Switch, etc.
Normally Open Momentary
dry contacts
1
2
3
4
5
6
Signal input
Signal common
Relay output (K2)
Relay output (K1)
24 VDC (+)
24 VDC (-)
3-5 Jumper wire
22ga or larger
copper wire only
(not provided)
Notes:
1. All switches, latches, and other accessaries should be
connected according to standard wiring instructions.
2. Recommend RF kit #573 for use with Executive
Feature.
Executive Feature
Operation:
Door is normally closed and latched.
Activating switch will open the door and the door will stay open
until the button is depressed again, then the door will close
and latch.
Jumper Settings
WITH POWER DISCONNECTED
, Place jumper on
pins 1 and 2 to activate the Executive Feature program.
L2
115Y
L1
115/230VAC IN
MOTOR OUT
L2
230Y
U
V
W
STATUS LEDS
PUSH PULL
SW501
ON
H/O TQ
H/O TM
OBSTR
SENS
P1
M/DLY
P2
1
2
1
6
COM
SNS
COM
PB
K1
K2
11
JMP503
NC
NO
TB501
F
F
Normal
operation
Executive
operation
J502
J502
1 2 3 4
1 2 3 4