The service engineer can configure the following functions onto the relays Rel2 (figure 4 no. 9.2)
and Rel3 (figure 4 no. 9.3):
Lighting (courtyard light) with shutdown delay after the end of the gate movement
Maintenance signal (maintenance required)
Additional electrical brake
Warning:
When assigning the functions to the individual relays it is necessary to ensure that
the outputs are not doubly configured. An output that has already been configured must first
be released from its previous function before it can be assigned another function.
4.4.1 Relay outputs with 24 V
DC
or with 230 V
AC
Control lamps with 24-volt supply voltage can be connected as shown in the following figure 8.
Figure 8: Connection of relay with 24 V
DC
Figure 9: Connection relay with 230 V
Warning:
The control system‘s maximum current capacity of 500 mA must be taken into consideration
when wiring the external 24 V supply.
There is a 230 V output for external cons
umers on the control system‘s power board (figure 3 No. 6)
that is protected with a glass tube fuse (6.3 A delay) (figure 3 No.7). 230 V consumers can also be
switched via this supply output and the relays. The connection of a corresponding control lamp or
blinking lamp can thus be established as shown in figure 9.
Warning:
The supply output‘s maximum current capacity must be taken into consideration during wiring.
Furthermore, the maximum load of 250 W must be observed for each individual relay.
The fuse (6.3 A delay) may only be replaced with a fuse with the same connection value.
Caution:
The relay outputs are separated from the safety extra-low voltage in the control system in a
way that conforms to standards. However, the individual relay connections amongst
themselves do not fulfil this requirement.
Therefore a mixed operation of the connection on the 230 V
AC
and 24 V
DC
relays is not
permissible (either all 230 V
AC
relays or all 24 V
DC
relays).