Asetek InRackCDU Installation, Operation & Maintenance Guide 2
1.
Product Introduction
Asetek InRackCDU is a data center, warm water, direct-to-chip (D2C), liquid cooling system that is
deployable at a rack level. The InRackCDU system consists of six major components:
1.
CDU Cabinet containing liquid-to-liquid heat exchanger and coolant reservoir
2.
CDU to CDM hoses
3.
Coolant Distribution Manifolds (CDM)
4.
Power supply for monitoring system
5.
Facility hose pair (not shown)
6.
Rail kit (not shown)
The first three components of the InRackCDU system are delivered pre-filled with server cooling liquid.
There is no need for data center staff to handle server cooling liquid when installing the InRackCDU or
when removing and replacing servers during maintenance. Tubes connect between the CDM and server
coolers with locking dripless quick connectors. These connectors seal immediately when disconnected
keeping the server coolant in the tube, CDM and server cooler.