Asetek InRackCDU Installation, Operation & Maintenance Guide 11
5.4
Connecting CDU Cabinet to CDM
The two CDM hoses are fixed to the CDU Cabinet. The top hose connects to the supply CDM (blue) while
the lower hose connects to the return CDM (red). Place the provided EPDM gasket between the flanges
on the hose and the CDM and install the Tri Clamp locking ring.
5.5
Mount Ventilation Tube for Reservoir
To secure atmospheric pressure, a venting tube must be mounted to the Quick Connector on the rear side
of the CDU cabinet. Remove the protection caps from the quick connector and ventilation tube, then
mount the tube as shown below.
The ventilation tube must be disconnected during transportation and should only be mounted at finale
location. When connection is complete, route the ventilation tube and the drain tube inside the rack down
to the floor.
If there is a water leak in the CDU cabinet, the drain will drain from the end of the drain tube. Please
prepare the drainage facilities at the facility side.
Attach venting tube
Drain tube