Asentria SiteBoss 530 User Manual
47
Alarm Enable
is an ON/OFF toggle to enable the CPE Down Event. Default setting is OFF.
Alarm Actions
displays the Actions List, a menu where the action string for the event is configured. This field will
be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to
in the Features chapter for more information.
Alarm Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 511, but trap
number can also be set in the range of 1000 – 1199 as needed.
Alarm Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in
is displayed, from which you can select one to be assigned to this alarm.
Return to Normal Actions
displays the Actions List, a menu where the action string for the event is configured.
This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have
been configured. Refer to
in the Features chapter for more information.
Return to Normal Trap Number
sets the trap number which can be useful when using SNMP trap managers that
employ a trap numbering system to help identify incoming traps. The default trap number for CPR Down Events
is 511, but any number in the alternate range of 1000 – 1199 can be used.
Return to Normal Class
sets the class for the alarm. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this alarm.
Event Message Settings
SiteBoss 530 - Event Message Settings
A) Include Date and Time [ON]
B) Include Site Name [ON]
C) Include Sensor ID [ON]
D) Include User Defined Name [ON]
E) Include User Defined State [ON]
F) Include Event Class [ON]
Include Date and Time / Site Name / Sensor ID / User Defined Name / User Defined State
/ Event Class
are
each ON/OFF toggles to permit customization of the event message that appears in SNMP traps, Emails, Tetra
modem callouts, SMS messages, pages, etc. sent by the S530. Default setting for each is ON.
Action Definitions
This menu is where you configure all of the actions possible when events are detected.
SiteBoss 530 - Actions Definition Menu
A) Hostname/IP Address 1 []
B) Hostname/IP Address 2 []
C) Hostname/IP Address 3 []
D) More Hostnames/IP Addresses []
E) Email Address 1 []
F) Email Address 2 []
G) Email Address 3 []
H) More Email Addresses []
I) Phone Number 1 []
J) Phone Number 2 []
K) Phone Number 3 []
L) Phone Number 4 []
M) Pager Number 1 []
N) Pager Number 2 []
O) Pager Number 3 []
P) Pager Number 4 []
Q) Action Settings
Содержание SiteBoss 530
Страница 6: ......