Asentria SiteBoss 420 User Manual
Deadband
– sets the range, in degrees, on either side of a temperature setting that prevents the event from
repeatedly going in and out of the "event state" as the actual temperature fluctuates above and below the temperature
setting. Default setting is 3 degrees.
Very High / High / Low / Very Low Temp
– are the settings for each of four temperature thresholds that the S420
can alarm on. If Alarm State is set to ON, and the temperature rises above the High and Very High settings, the Alarm
Actions will take effect. Same process if the temperature drops below either the Low or Very Low settings. Default
settings are: Very High (120), High (100), Low (40), Very Low (32).
Very High / High / Low / Very Low Severity
– displays a drop down menu of four descriptive words – Info, Minor,
Major, Critical – that allow you to assign a severity rating to this alarm. This word will appear in an SNMP Trap alert,
but does not appear in an Email alert. Default setting for all is “Info”.
Humidity Sensor
Alarm Name
– sets the name of the alarm that is generated when the humidity rises above or drops below the set
thresholds. This name is included in the Email and/or the SNMP Trap generated. (Max length 32 chars)
Currently
– displays the current humidity.
Alarm State
– is an On/Off toggle to set whether the S420 should take an alarm action if the current humidity exceeds
any of the Very High / High / Low / Very Low thresholds shown to the right. Default setting is Off.
17