AGC CONTROL SCREEN
Automatic Gain Control is: ENABLED
Enable Disable Exit
KW-HOUR METER
kW-Hours:XXXXXXX.XX Run Time. XX:XX:XX:XX
Max. Level: XXX.X% Max. Power: XX.XXkW
Clear Exit
7.6
AGC CONTROL
Press the
SHORE POWER + F4
buttons to access the Automatic Gain Control (AGC)
CONTROL display.
This function enables or disables AGC. Press the Enable
(F1)
button to enable the feature, the
Disable
(F2)
button to disable the feature, and the Exit
(F5)
button to save the settings and exit.
Default
Range
Automatic Gain Control
Enabled
Enabled, Disabled
Application: this function will compensate for changes in output voltage not already corrected by
hardware and software calibration such as load-dependent output voltage variances. This function
should be disabled before calibrating the hardware oscillator and current compensation pots on the
Modulator Interface PCB (usually only done when initially setting the output voltage configuration
at the factory). It must be disabled when using Converter Output Impedance Control (see page 50).
7.7
kW-HOUR METER AND MAXIMUM POWER LEVEL DISPLAY
Press the SHORE POWER + CONVERTER POWER buttons to access the Automatic KW-HOUR
METER and maximum power level display.
Press the Clear
(F1)
button to clear all data and the Exit
(F5)
button to exit.
Application: this reference kW-hour meter can be used to check the billing received in a marina.
Immediately after connecting shore power and turning the converter's red disconnect switch, clear