TRH22

RELATIVE HUMIDITY AND  

TEMPERATURE PROBE

OPERATING INSTRUCTIONS

Vr 01 (ENG) - 19/07 - cod.: ISTR-MTRH22-ENG01

ASCON TECNOLOGIC S.r.l.

Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY 
Tel.:  +39 0381 69871 - Fax: +39 0381 698730 

http:\\www.ascontecnologic.com

 

[email protected]

PREFACE

D

D

This manual contains the information necessary for 
the product to be installed correctly and also instruc-
tions for its maintenance and use; we therefore recom-
mend that the utmost attention is paid to the following 
instructions and to save it

This document is the exclusive property of Ascon Tecnologic 
S.r.l. which forbids any reproduction and divulgation, even 
partially, of the document, unless expressly authorized.
Ascon Tecnologic S.r.l. reserves the right to make any formal 
or functional changes at any moment and without any notice.
Ascon Tecnologic S.r.l. and its legal representatives do not 
assume any responsibility for any damage to people, things 
or animals deriving from violation, wrong or improper use or 
in any case not in compliance with the instrument features.

D

D

Whenever a failure or a malfunction of the device 
may cause dangerous situations for persons, thing 
or animals, please remember that the plant has to be 
equipped with additional electromechanical devices 
which will guarantee safety.

1.  DESCRIPTION

1.1 

General Description

The TRH 22 is a relative humidity probe (of capacitive-digital 
type) and temperature (of thermistor-digital type) with normal-
ized current output signals 4 ÷ 20 mA with 4 wires (2 + 2).

1.2 

Probe description

2

1

Sensor protective cap;

Cable 4 x 0.25 mm

2

.

2.  INSTALLATION AND USAGE  WARNINGS

D

D

The TRH22 probe 

DOES NOT WORK

 when only the 

temperature sensor is connected and powered.  To work 
properly both the probe sensors, relative humidity and 
temperature, must be connected and powered.

2.1 

Admitted use

D

D

The instrument has been projected as measure trans-
ducer.  It must be reminded that the user has to take 

care that the electromagnetic rules are being respected also 
after the instrument installing, eventually using proper filters.

2.2 

Mechanical mounting

The instrument, into cylindrical case, is designed for wall 
mounting by provided clip.

 

Install the instrument as far as possible from electromagnetic 
sources as motors, power relay, relays, electrovalves, etc..

 

The signal cables of the device must be routed separately 
from the power cables.

 

Avoid placing the probe in places where strong corrosive 
and polluting gases can be present and make sure that the 
probe is in an ventilated position.

D

D

Should be necessary to remove the protective cap, do 
not cause any mechanical stress to the sensor and 
absolutely avoid touching the sensor surface.

2.3 

Dimensions

 [mm]

2.3.1 

Mechanical dimensions

1500

185

20

2.4 

Electrical connections

Make electrical connections according to the following 
diagrams, checking that the power supply is the same as 
indicated on the instrument.
The probe can be powered by the instruments to which is 
connected or by an external power supply.
Check then if the measure instrument is equipped with a 
voltage output 8 ÷ 24 VDC able to supply at least 20 mA, 
otherwise connect the probe to a 8 ÷ 24 VDC external power 
supply able to supply 40 mA and connecting it as described 
following the wiring diagrams.
It is strongly recommended that cables with proper insulation, 
according to the working voltages and temperatures, be used.
Furthermore, the input cable of the probes has to be kept sepa-
rate from line voltage wiring.  If some cables used for the wiring 
should be shielded, it is recommended to 

connect the shield  

to ground at one side only

.

2.5 

Electrical wiring diagram

2.5.1 

Wiring diagram with instrument supply

INPUT -

4 ÷ 20 mA

INPUT +

4 ÷ 20 mA

OUT V

+8 ÷ 24 VDC

+

+

GREEN

WHITE

TRH 22

YELLOW

BRO WN

Supply HUMIDITY

+ 8 ÷ 24 VDC

OUT TEMPERATURE

4 ÷ 20 mA

OUT HUMIDITY

4 ÷ 20 mA

T

V+H

V+T

RH

Supply TEMPERATURE

+8 ÷ 24 VDC

INPUT -

4 ÷ 20 mA

INPUT +

4 ÷ 20 mA

OUT V

+8 ÷ 24 VDC

Humidity probe

Temperature probe