Installation

Manual

Contents

- Installation

- Electrical connections

- How to Order

CANopen  

Communication Module

model

 

exCOM

Code. ISTR_I_exCOM_E_01_--

E

Installation

Wiring rules

Description

Plugs of all terminals

Flexible cable section:

Pitch 3.5 mm: 

0.14... 1.5 mm

²

 (AWG28... AWG16)

L

Stripped wire

L:

 7mm

Flat blade screwdriver Pitch 3.5 mm: 0.4 x 2.5 mm

Tightening torque

Pitch 3.5 mm: 0.22... 0.25 Nm

Technical data:

 - The green terminals are pitch 3.5 male connectors, the correspondent female 

connectors have screw or spring terminals for connecting the wires;

 - Made with self extinguishing material as required by UL94 V0 standard;

 - Overvoltage cathegory/pollution degree II/2;

 - Max. load current/section 8A/2.5mm² at 65°C;

 - Test pulse voltage: 4 kVp.

Suggested wires routing

Conduit f

or lo

w le

vel sensor cab

les

Conduit f

or supply and output cab

les

nP4.0

ETHERNET

X12

D-   D+      TX   RX

GND

SW1

USB

X11

X13  

COM1

+            -

DIG 24V

+        -

DIG 24V

X5

D01         D03        D05        D07      CNT1

        D02        D04       D06        D08       CNT2

D09        D11        D13        D15

        D10        D12       D14        D16

X6

X7

AO1 GND AO2

mA V       V mA

X9

AO3 GND AO4

mA V       V mA

X10

  5V 12V  AI1     AI2     AI3     AI4
RATIO     

+   -   +   -    +    -    +    -

X8

 PWR 24V

  -          +

X1

C       OP1   OP2

X2

X3

   GND D- D+

X4

  

COM2

SW2

COMS

US

B

MS

G

RU

N

PW

R

C      OP3   OP4

POL+

POL-

NONE

TERM

CAN_H

CAN_L

CAN_GND

T0

STS

X0

exCOM

100

100

DO cables

Power cables

Comm.s cable

AI/AO cables

Digital I/Os cables

100

100

A

Despite the fact that the instrument has been designed to work in an 

harsh and noisy environment, it is strongly recommended to follow 

the following suggestions. 

All wirings must comply with the local regulations.
Avoid to use electromagnetic contactors, power relays and high power motors nearby.
Avoid power units nearby, especially if controlled in phase angle.
Keep the low level sensor input wires away from power lines and output cables. 
Power lines and output cables must also be at 

100 mm

 (min.) away from the CPU. 

If this is not achievable, use shielded cables on the sensor inputs, with the shield 

connected to earth at only one side.

A

Warning! 

Whenever a failure or a malfunction of the device may cause dangerous 

situations for persons, things or animals, please remember that the plant 

must be equipped with additional devices which will guarantee safety.

Dimensions (mm)

Rail mounting 
DIN 35 x 7.5
(EN 50022)

88

70

 46

78.65

28

21.55

Mounting position

-  Mount the module vertically;

-  In order to help the air ventilation flow, 

respect the distances between mod-

ules and walls or other modules.

min. 60

55

min. 100

min. 80

Mounting position (mm)

Disposal

The appliance (or the 

product) must be 

disposed of separately 

in compliance with the 

local standards in force 

on waste disposal.

DIN rail Placing

Mounting the exCOM on the DIN rail

1

 Open the 2 spring slides at the top 

and bottom part of the exCOM;

2

 Insert the groove of the module on 

the DIN rail

3

 Close the 2 spring slides;

1

2

3

3

4

4

5

5

Removing the exCOM from DIN rail

4

 

Switch OFF the CPU Power Supply

Open the spring slides by inserting a 

flat-blade screwdriver as indicated;

5

 Remove the EXCOM from the DIN rail.

1

2

3

3

4

4

5

5

Operating conditions

Environmental condition

B

Suggestion

Operating 
conditions

T

Temperature 

-20...+50°C

%Rh

Rh: 5... 95%  

non condensing

Special  
conditions

T

Temperature 

> 50°C

Use forced  
ventilation

%Rh

> 95% RH

Warm up

P

Conducting  
atmosphere

Use filter

Forbidden 

conditions

C

Corrosive  
atmosphere

E

Explosive 

atmosphere

- For indoor use only. 

- Max. usage altitude: 2000 m 

  on the sea level.