background image

Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 6

5.2.2 

Turbo/Normal/Eco operation selection

Turbo

 mode can be selected manually:

 

Pressing the 

/

 key if parameter 

tUF

 = 

4

;

 

Pressing the 

/Aux

 key if parameter 

tFb

 = 

4

;

 

From digital input if parameter 

i.Fi

 = 

8

;

Turbo

 mode can be selected automatically:

 

Leaving Eco mode (only if 

rHC

 = 

C3

)

 

Every time the instrument is switched ON (only if 

rHC

 = 

C3 

and Pr1 > SPE + rEd)

The instrument quits Turbo mode and returns to normal mode 
automatically at the end of 

rtC

 time or manually using the 

programmed command (key or digital input).
Setting 

rHC

 = 

C3 

gives the following operating cycle:

At power ON, the instrument starts in the mode it was in 
when it was switched OFF (Normal or “Eco”) unless the tem-
perature at power ON is > SPE + rEd.  In this case (see fig.) 

Turbo

 cycle is automatically initiated.

After time 

rtC

 the instrument automatically swiyches to 

Nor-

mal

 mode.  If the door is opened frequently, the instrument 

remains in 

Normal

 mode.  If however the door is not opened 

for time set at 

iEt

 parameter, it automatically switches to 

Eco

 mode.

The instrument remains in 

Eco

 mode until the door is 

opened again or, if set, until the time-out 

itt

.

On leaving 

Eco

 mode the instrument therefore runs a 

Turbo

 

cycle to allow product temperature to be restored, after 
which it reverts to 

Normal

 mode and so on.

Temp.

SPE

Eco

SP

SPH

Turbo

rHd

rEd

itt (2)

rtC

rtC

time

Normal

Turbo

ECO

Turbo

iEt (1)

rd

Pr1

The time iEt is reset every time the door is opened and 
in the case shown the door is always closed.

The time 

itt

 stops when the door is opened and the 

instrument immediately switches to 

Turbo

 mode.  In the 

case shown, the door is always closed.

When in 

Turbo

 mode, the instrument shows the characters 

trb

 alternated to the normal display indication.

The normal Set Point 

SP

 can be set to a value between the 

one set with parameter 

SLS

 and the one set with parameter 

SHS

 while the Economic Set Point 

SPE

 can be set to a value 

between the one set with parameter 

SP

 and the one set with 

parameter 

SHS

; the Turbo Set point (

SHP

) can be set to a 

value between the one set with parameter 

SLS

 and the one 

set with parameter 

Sp

.

Note: 

In the following examples the Set Point is generally 
indicated as 

SP

 and the differential as 

rd

 however the 

instrument will act according to the Set Point and the 
differential selected as active.

5.3 

Measure and display configuration

With parameter 

iuP

 it is possible to select the tempera-

ture engineering unit and the desired measure resolution 
(

C0

 = °C/1°; 

C1 

= °C/0.1°; 

F0

 = °F/1°; 

F1

 = °F/0.1°).

The instrument allows the measure calibration, which can 
be used to recalibrate the instrument according to applica-
tion needs, the calibration is made by using parameters 

iC1

 

(input Pr1), 

iC2

 (Pr2 input) and 

iC3

 (Pr3 input).

Parameters 

iP2

 and/or 

iP3

 allows to select the instrument 

usage of 

Pr2

/

Pr3

 measure as:

EP

  Evaporator probe: used to managing the defrost and the 

evaporator fans (see relative functions).

Au

  Auxiliary probe;

DG

  Digital Input (see the Digital input functions).

If 

Pr2

/

Pr3

 input is not used, set 

iP2

/

ip3

 = 

oF

.

Two inputs cannot set to perform the same function.   
If two inputs are set to do the same function, this is done 
only by the 

P2

 input.

Using 

iFt

 parameter can be set a software filter for measur-

ing the input values in order to decrease the sensibility to rapid 
temperature changes (increasing the sampling time).
Through the 

idS

 parameter is possible to set the variable 

normally displayed:

P1 Pr1 

probe measurement;

P2 Pr2 

probe measurement;

P3 Pr3 

probe measurement;

SP 

Active Set Point;

EC

  Pr1 probe measure if the instrument is in Normal mode, 

the label 

Eco

 if the instrument is in (

Eco mode

);

OFF 

If the numerical display must be switched off (

oF

).

When one of the measures is displayed (

idS

 = 

P1

/

P2

/

Ec

the 

iCU

 parameter allows to set an offset that is to be applied 

only to the displayed variable (all controls will always made 
according to the correct temperature value, changed only by 
the calibration parameters).
Regardless of what is set at 

idS

 parameter, all the measure-

ment variables can be shown pressing the 

 key.

The display alternately shows the code that identifies the 
variable and its value.  The variables are:

Pr1

 Probe 1 measurement;

Pr2

 Probe 2 measurement (on/oFF if Pr2 is a Digital input);

Pr3

 Probe 3 measurement (on/oFF if Pr3 is a Digital input);

Lt

  Minimum stored Pr1 temperature;

Ht

  Maximum stored Pr1 temperature.

The Peak (min./max.) temperature values of 

Pr1

 probe are 

NOT

 stored in case of power failure.  While the controller is 

showing the peak values, these can be reset pressing the 

 

key for 3 s.  At the end of the key 

 pressure, the display 

shows “

---

” for an instant to indicate that the min./max. val-

ues have been erased and the new peak is the temperature 
read in that moment.
The system exits the variable dosplay mode after 15 s from 
the last 

 key pressure.

It is also noted that the 

Pr1

 probe display can also be changed 

by “

Defrost display lock

” function via the 

ddL

 parameter  

(see the Defrost function).

Содержание e33

Страница 1: ...rvals by temperature reaching or by con tinuous compressor operation time through stopping the compressor electric heating or hot gas cycle inversion The instrument has up to 3 relay outputs and up to...

Страница 2: ...al mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it press the key to increase the value or to decrease...

Страница 3: ...protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The dp...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ut 1 R 10 4 A 10 A Res 8 3 A Out 2 8 4 A 2 A Gen Use 5 1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the...

Страница 6: ...ith parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The instrument allows the measure calibration which can...

Страница 7: ...control the evaporator fans Au To control the auxiliary device At To control a silenceable alarm device through a contact that is NO in normal operation then closed when the alarm sounds AL To control...

Страница 8: ...output In the event of a probe error it is possible to set the instru ment so that that the output continues to work in cycles according to the times programmed with parameter rt1 activation time and...

Страница 9: ...the first defrost after power ON can be set with parameter dSd This allows to perform the first defrost to a different interval from ddi time To force the instrument to perform a defrost cycle at eac...

Страница 10: ...y the EP probe is higher than the one set at param eters dtS and also dtE the defrosting is inhibited dtE dts Defrost dF off off off ON ON A B Temp time C NO defrost dde ddi dSd Defrost ddi dSd ddi dS...

Страница 11: ...change Remember that the fans functioning can be conditioned by the Door open function by the digital input 5 10 Alarm functions The alarm conditions of the instrument are Probe errors E1 E1 E2 E2 and...

Страница 12: ...ON Hi Lo Pr1 or they assume the values SP AHA and SP ALA if the alarms are relative AAy 2 4 6 8 AHA SP ALA off off off ON ON Hi Lo AL AAd AAd Temp time Pr1 The maximum and minimum temperature alarms c...

Страница 13: ...ment are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info pleas...

Страница 14: ...r 2 Open Door with Fan Lock 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 9 Defros...

Страница 15: ...1 59 s 1 99 min 10 41 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59...

Страница 16: ...bled 1 Active for alarms only 2 Active for key pressed only 3 Active for alarms and key pressed oF 65 oFo Auxiliary output function oF Function disabled 1 Control output ot delayed 2 Manual activation...

Страница 17: ...ults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10 AC...

Страница 18: ...e NTC 103AT11 11 INSTRUMENT ORDERING CODE a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R Out1 Relay SPST NO 30A AC1 for resistive l...

Страница 19: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 19...

Страница 20: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 20...

Отзывы: