Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 5

4.3 

Electrical connections

Carry out the electrical wiring by connecting only one wire to 
each terminal, according to the following diagram, checking 
that the power supply is the same as that indicated on the 
instrument and that the load current absorption is no higher 
than the maximum electricity current permitted.
As the instrument is built-in equipment with permanent con-
nection inside housing, it is not equipped with either switches 
or internal devices to protect against current overloads: the 
installation will include an overload protection and a two-
phase circuit-breaker, placed as near as possible to the in-
strument and located in a position that can easily be reached 
by the user and marked as instrument disconnecting device 
which interrupts the power supply to the equipment.
It is also recommended that the supply of all the electrical cir-
cuits connected to the instrument must be protect properly, us-
ing devices (ex. fuses) proportionate to the circulating currents.
It is strongly recommended that cables with proper insulation, 
according to the working voltages and temperatures, be used.
Furthermore, the input cable of the probe has to be kept sepa-
rate from line voltage wiring.  If the input cable of the probe is 
screened, it has to be connected to the ground at only one side.
Whether the instrument is a 12 V version (Power supply code 
F) it is recommended to use an external TCTR transformer, or 
with equivalent features (class II insulation) and to use only one 
transformer for each instrument because there is no insulation 
between supply and input

D

D

We recommend that a check should be made that the 
parameters are those desired and that the application 
functions correctly 

before connecting the outputs to 

the actuators

 so as to avoid malfunctioning that may 

cause irregularities in the plant that could cause dam-
age to people, things or animals.

4.3.1 

Electrical wiring diagram

Internal

Buzzer

Pr1

Pr3

Pr2

Digital

Input

Power

supply

INPUTS

NO

NO

NO

NC

C

Out2

Out1

Out3

OUTPUTS

(12 A max. for removable connectors models)

16 FLA

96 LRA

15 A Res.

EN

30 (15) A

61810

Out 1 (H):

15 (15) A

5 FLA

30 LRA

12 A Res.

16 (9) A

Out 1 (R):

10 (4) A

10 A Res.

8 (3) A

Out 2:

8 (4) A

2 A Gen. Use

5 (1) A

Out 3:

2 (1) A

60730

EN

UL

5.  FUNCTIONS

5.1 

ON/Stand-by function

Once powered the instrument can assume 2 different conditions:

ON

:  Means that the controller uses the control functions.

STAND-BY:   

Means that the controller uses no control function and 
the display is turned off except for the Stand-by LED.

The transition between Standby and ON is equivalent to 
power ON the instrument providing the electrical power
In case of power failure, the system always sets itself in the 
condition it was in before the black-out
The ON/Stand-by function can be selected:

 

With the key 

/

 pressed for 1 s if 

tUF

 = 

3

;

 

With the key 

/Aux

 pressed for 1 s if 

tfb

 = 

3

;

 

Using the Digital Input if parameter 

iFi

 = 

7

;

5.2 

Normal, Economic and Turbo operation

This tool allows to pre-set 3 different Setpoints, 

Normal

 - 

SP

Economic

 (or Eco) - 

SPE

 and 

Turbo

 SPH.

Associated with each Setpoint there is the relative differential 
(hysteresis): 

Normal

 - 

rd

Eco

 - 

rEd

 and 

Turbo

 - 

rHe

.  Switch-

ing between the various modes can be 

automatic

 or 

manual

.

5.2.1 

Normal/Eco operation selection

This function can be used when you need to switch two func-
tional temperatures (eg. Day/Night or week-day/week-end).

Temp.

Pr1

SPE

SP

Door

rd

rEd

iEt

time

“Norm.”

DAY (Shop open)

DAY (Shop open)

NIGHT (Shop closed)

“Norm.”

“ECO”

The Normal/Eco operation can be selected in manual mode:

 

Using the 

/

 key if parameter 

tUF

 = 

2

;

 

Using the 

/Aux

 key if parameter 

tFb

 = 

2

;

 

Using the Digital Input if parameter 

iFi

 = 

6

.

The Normal/Eco operation can be selected in automatic mode:

 

Elapsed the 

iEt

 time after the door has been closed 

(Normal/Eco switching).

 

At door opening if the 

SPE

 Setpoint is activated by 

iEt

 

parameter (Eco/Normal switching).

 

Elapsed the 

itt

 time after the door has been closed and 

from the activation of 

SPE

 Setpoint by 

iEt

 parameter 

(Eco/Normal switching).

To use this function, it is necessary to set the Digital Input as: 

iFi

 = 

1

2

 or 

3

.

If 

iEt

 = 

oF

 the selection of Eco/Normal modes via the digital 

input is disabled.
If 

itt

 = 

oF

 the time-out switching from Eco to Normal mode 

is disabled.
Switching to Economic mode is indicated by the label 

Eco

.  

When 

idS

 = 

Ec

 the Economic mode is pointed out with a 

fixed 

Eco

 label otherwise the label 

Eco

 appears every 10 s 

alternated to the display set with parameter 

idS

.

When used as a shop widow light (

oFo

 = 

3

), 

Eco

 mode 

selection is always associated with the Auxiliary Output turn 
OFF function.

Содержание e33

Страница 1: ...rvals by temperature reaching or by con tinuous compressor operation time through stopping the compressor electric heating or hot gas cycle inversion The instrument has up to 3 relay outputs and up to...

Страница 2: ...al mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it press the key to increase the value or to decrease...

Страница 3: ...protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The dp...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ut 1 R 10 4 A 10 A Res 8 3 A Out 2 8 4 A 2 A Gen Use 5 1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the...

Страница 6: ...ith parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The instrument allows the measure calibration which can...

Страница 7: ...control the evaporator fans Au To control the auxiliary device At To control a silenceable alarm device through a contact that is NO in normal operation then closed when the alarm sounds AL To control...

Страница 8: ...output In the event of a probe error it is possible to set the instru ment so that that the output continues to work in cycles according to the times programmed with parameter rt1 activation time and...

Страница 9: ...the first defrost after power ON can be set with parameter dSd This allows to perform the first defrost to a different interval from ddi time To force the instrument to perform a defrost cycle at eac...

Страница 10: ...y the EP probe is higher than the one set at param eters dtS and also dtE the defrosting is inhibited dtE dts Defrost dF off off off ON ON A B Temp time C NO defrost dde ddi dSd Defrost ddi dSd ddi dS...

Страница 11: ...change Remember that the fans functioning can be conditioned by the Door open function by the digital input 5 10 Alarm functions The alarm conditions of the instrument are Probe errors E1 E1 E2 E2 and...

Страница 12: ...ON Hi Lo Pr1 or they assume the values SP AHA and SP ALA if the alarms are relative AAy 2 4 6 8 AHA SP ALA off off off ON ON Hi Lo AL AAd AAd Temp time Pr1 The maximum and minimum temperature alarms c...

Страница 13: ...ment are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info pleas...

Страница 14: ...r 2 Open Door with Fan Lock 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 9 Defros...

Страница 15: ...1 59 s 1 99 min 10 41 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59...

Страница 16: ...bled 1 Active for alarms only 2 Active for key pressed only 3 Active for alarms and key pressed oF 65 oFo Auxiliary output function oF Function disabled 1 Control output ot delayed 2 Manual activation...

Страница 17: ...ults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10 AC...

Страница 18: ...e NTC 103AT11 11 INSTRUMENT ORDERING CODE a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R Out1 Relay SPST NO 30A AC1 for resistive l...

Страница 19: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 19...

Страница 20: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 20...

Отзывы: