Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 12

5.10.1  Temperature alarms

The temperature alarm works according to 

Pr1

 or 

AU

 probes 

measurement, the type of alarm set in the parameter 

AAy

 the 

alarm thresholds set in parameters 

AHA

 (maximum alarm) 

and 

ALA

 (minimum alarm) and the relative differential 

AAd

.

Through parameter 

AAy

 it is possible to set the alarm thresh-

olds 

AHA

 and 

ALA

 as absolute or relative to the active Set 

Point, must be related to Pr1 or Au probes and if the message 

Hi

 (High alarm) and 

Lo

 (Low Alarm) are to be displayed at 

alarm intervention.
Depending on the desired alarm operating mode, parameter 

AAy

 can be set as:

Absolute alarms referred to probe Pr1, displays 

Hi

/

Lo

;

Relative Alarms referred to probe Pr1, displays 

Hi

/

Lo

;

Absolute alarms referred to probe Au, displays 

Hi

/

Lo

;

Relative Alarms referred to probe Au, displays 

Hi

/

Lo

;

Absolute alarm referred to probe Pr1, displays no labels;

Relative alarm referred to probe Pr1, displays no labels;

Absolute alarm referred to probe Au, displays no labels;

Relative alarm referred to probe Au, displays no labels.

Using some parameters it is also possible to delay the ena-
bling and the intervention of these alarms.
These parameters are:

APA

  Temperature alarm exclusion time on switching ON the 

instrument if the instrument is in alarm status when it 
is switched ON.  If the instrument is not in alarm status 
when it is switched on the time 

APA

 it is not considered.

AdA

 

Temperature alarm exclusion time at the end of de-
frost cycle (and, if programmed, after the draining) or 
after a continuous cycle.

AAt

  Temperature alarms delay activation time.  Tempera-

ture alarms are enabled at the end of the exclusion 
times and are activated after the 

AAt

 time when the 

temperature measured by the probe exceeds or goes 
below the respective maximum and minimum alarm 
thresholds.  The alarm thresholds are those set at 
parameters 

AHA

 and 

ALA

 when the alarms are set as 

absolute (

AAy

 = 

1

3

5

7

).

Temp.

AHA

AAd

time

AL

ALA

AAd

off

off

off

ON

ON

Hi

Lo

Pr1

or they assume the values [

SP

 + 

AHA

] and [

SP

 + 

ALA

if the alarms are relative (

AAy

 = 

2

4

6

8

).

AHA

SP

ALA

off

off

off

ON

ON

Hi

Lo

AL

AAd

AAd

Temp.

time

Pr1

The maximum and minimum temperature alarms can be disa-
bled by setting the related parameters 

AHA

 and 

ALA

 = 

oF

.

The temperature alarms are signalled lighting up the alarm 
LED ( ) and, if configured, also with the buzzer.

5.10.2  External alarm from digital input

The instrument can signal an alarm external to the instrument 
using the digital input setting 

iFi

 = 

4

 or 

5

.  The instrument 

signals the alarm flashing with the Alarm LED and, if config-
ured, turns ON the output set as Alarm output.
Mode 

iFi

 = 

4

 operates no action on the control output, 

while 

iFi

 = 

5

 deactivates the control outputs at digital input 

intervention.

5.10.3  Open door alarm

The instrument can signal the open door alarm coondition using 
the digital input setting 

iFi

 = 

1

2

 and 

3

.  As the digital input is 

activated, the instrument signals that the door is open showing 
on the display the 

oP

 label alternated to the variable set with 

parameter 

ids

.

After the delay set with parameter 

AoA

 the instrument signals 

the Open Door alarm with the configured devices (buzzer and/
or Output), lighting up the LED   while showing the 

oP

 label.  

At the open door alarm intervention are also re-activated the 
inhibited outputs (compressor).

5.11  Function of keys 

/  and 

/Aux

Two of the instrument keys, in addition to their normal func-
tions, can be configured to operate other commands. The 

/

 key function can be defined using the 

tUF

 parameter 

while the 

/Aux

 key via parameter 

TFb

.  Both parameters 

have the same possibilities and can be configured to perform 
the following functions:

oF

 The key carries out no function;

Pressing the key for at least 1 s, it is possible to enable/
disable, if configured, the auxiliary output (

oFo

 = 

2

);

Pressing the key for at least 1 s, can be sequentially 
select a 

normal

 or 

eco

 operating mode (

SP

/

SPE

).  

A selection has been made the display shows for about 
1 s the active Set Point code (

SP

 or 

SPE

);

Pressing the key for at least 1 s is possible to switch the 
instrument from 

ON

 to 

Stand-by

 state and vice-versa;

Pressing the key for at least 1 s activates/deactivates a 
Turbo cycle.

Содержание e33

Страница 1: ...rvals by temperature reaching or by con tinuous compressor operation time through stopping the compressor electric heating or hot gas cycle inversion The instrument has up to 3 relay outputs and up to...

Страница 2: ...al mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it press the key to increase the value or to decrease...

Страница 3: ...protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The dp...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ut 1 R 10 4 A 10 A Res 8 3 A Out 2 8 4 A 2 A Gen Use 5 1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the...

Страница 6: ...ith parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The instrument allows the measure calibration which can...

Страница 7: ...control the evaporator fans Au To control the auxiliary device At To control a silenceable alarm device through a contact that is NO in normal operation then closed when the alarm sounds AL To control...

Страница 8: ...output In the event of a probe error it is possible to set the instru ment so that that the output continues to work in cycles according to the times programmed with parameter rt1 activation time and...

Страница 9: ...the first defrost after power ON can be set with parameter dSd This allows to perform the first defrost to a different interval from ddi time To force the instrument to perform a defrost cycle at eac...

Страница 10: ...y the EP probe is higher than the one set at param eters dtS and also dtE the defrosting is inhibited dtE dts Defrost dF off off off ON ON A B Temp time C NO defrost dde ddi dSd Defrost ddi dSd ddi dS...

Страница 11: ...change Remember that the fans functioning can be conditioned by the Door open function by the digital input 5 10 Alarm functions The alarm conditions of the instrument are Probe errors E1 E1 E2 E2 and...

Страница 12: ...ON Hi Lo Pr1 or they assume the values SP AHA and SP ALA if the alarms are relative AAy 2 4 6 8 AHA SP ALA off off off ON ON Hi Lo AL AAd AAd Temp time Pr1 The maximum and minimum temperature alarms c...

Страница 13: ...ment are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info pleas...

Страница 14: ...r 2 Open Door with Fan Lock 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 9 Defros...

Страница 15: ...1 59 s 1 99 min 10 41 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59...

Страница 16: ...bled 1 Active for alarms only 2 Active for key pressed only 3 Active for alarms and key pressed oF 65 oFo Auxiliary output function oF Function disabled 1 Control output ot delayed 2 Manual activation...

Страница 17: ...ults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10 AC...

Страница 18: ...e NTC 103AT11 11 INSTRUMENT ORDERING CODE a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R Out1 Relay SPST NO 30A AC1 for resistive l...

Страница 19: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 19...

Страница 20: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 20...

Отзывы: