5.9 

Evaporator fans control

The control of the evaporator fans on the output configured as 

Fn

 depends on some specific control statuses of the instrument 

and the temperature measured by the evaporator probe (

EP

).

In the case that the evaporator probe is not used or in error, 
the 

Fn

 output is activated only depending on parameters 

Ftn

FtF

 and 

FFE

.

Parameters 

Ftn

 and 

FtF

 can be used to determine the behavior 

of the evaporator fans when the 

ot

 outupt (compressor) is 

OFF

.

When 

ot 

output is 

OFF

, it is possible to set the instrument so 

that that the 

Fn 

output continues working in cycles according 

to the times programmed at parameters 

Ftn

 (fan activation 

time) and 

FtF

 (fan deactivation time).

When output 

ot

 is switched 

OFF

 the instrument activates the 

output 

Fn

 for the time 

Ftn

, then deactivates it for the time 

FtF

 and so on whilst the otuput 

ot

 remains 

OFF

.

Programming 

Ftn

 = 

oF

 the output 

Fn

 in 

ot

 

OFF

 condition 

remains switched 

OFF

.

Programming instead 

Ftn

 to any value and 

FtF

 = 

oF

 the 

output 

Fn

 when 

ot

 in 

OFF

 condition remains switched 

ON

.

The parameter 

FFE

 decides whether the fans must always 

be switched 

ON

 independently of the defrosting status 

(

FFE

 = 

on

) or switched 

OFF

 during defrosting (

FFE

 = 

oF

).

In this later case, it is possible to delay the start up of the 
fans even after the end of the defrosting of the time set in the 
parameter 

FFd

.  When this delay is active the LED   flash-

ing to point out that the delay is in progress.
When the evaporator probe is used the fans, as well as be-
ing conditioned by the parameters 

Ftn

FtF

 and 

FFE

, are 

also conditioned by a temperature control.
It is possible to determine whether the fans should be disabled 
when the temperature measured by the evaporator probe is 
higher than the 

FFL

 parameter (too hot) or even when it is 

lower than the 

FLF

 parameter (too cold).

The relative differential that can be set in parameter 

FdF

 is 

also associated with these parameters.

FLF

FFL

Temp.

FdF

FdF

time

off

off

off

ON

ON

Ep

Fan

Note: 

It is necessary to pay attention to the correct use of 
this fans temperature control functions because in 
the typical application of refrigeration the stop of the 
evaporator fans stops also the thermal exchange.

Remember that the fans functioning can be conditioned by 
the 

Door open

 function by the digital input.

5.10  Alarm functions

The alarm conditions of the instrument are:

 

Probe errors 

E1

-E1

E2

-E2

 and 

E3

-E3

;

 

Temperature alarms 

Hi

 and 

Lo

;

 

External alarm 

AL

;

 

Door open 

oP

.

The alarm functions acts on LED  , on the internal buzzer, 
if present and configured by the 

obu

 parameter and on the 

desired output if configured by parameters 

oo1

oo2

 or 

oo3

.

Any active alarm condition is signaled lighting up the LED  , 
while the acknowledged alarm status is shown by flashing the  
LED  .
The buzzer (if present) can be configured to point out the alarms 
by programming parameter 

obu

 = 

1

 or 

3

 and always acts to 

signal the acknowlegeable alarms.  This means that, when 
activated, it can be switched 

OFF

 by briefly pressing any key.

The possible selections of output parameters for the alarm 
signalling function are:

At

  When the output is to be activated in alarm condition and 

can be deactivated manually by pressing any key of the 
instrument (typical application for an acoustic signal);

AL

  When the output is to be activated in alarm condition but 

cannot be deactivated manually; it is then deactivated 
only when the alarm status ceases (typical application 
for a light signal);

An

  When the output is to be activated in alarm condition 

and that remains active even when the alarm status 
has ceased.  The disabling action (recognition of stored 
alarm) can only be carried out manually by pressing any 
key when the alarm status has removed (typical applica-
tion for light signal).

-t

  when one wants the function described as At but with 

an inverse function (output activated in normal condition 
and disabled in alarm status).

-L

  This alarm function is similar to 

AL

 but with inverse logic 

(output active in normal conditions and disabled in alarm 
status).

-

n

  This alarm function is similar to 

An

 but with inverse 

working logic (output active in normal conditions and 
disabled in alarm status).

The instrument offers the possibility to have the alarm 
memory function activated via the parameter 

AtA

.

If 

AtA

 = 

oF

, the instrument cancels the alarm signal when 

the alarm status ends, if instead 

AtA

 = 

on

, the instrument 

maintains the alarm signal also when the alarm status ends.
To cancel the alarm memory signal, press any key.
It must be remembered that if an output function is desired 
with an alarm memory (

oo1

/

oo2

/

oo3

 = 

An

/

-An

) it is 

necessary to set the parameter 

AtA

 = 

on

.

Содержание e33

Страница 1: ...rvals by temperature reaching or by con tinuous compressor operation time through stopping the compressor electric heating or hot gas cycle inversion The instrument has up to 3 relay outputs and up to...

Страница 2: ...al mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it press the key to increase the value or to decrease...

Страница 3: ...protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The dp...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ut 1 R 10 4 A 10 A Res 8 3 A Out 2 8 4 A 2 A Gen Use 5 1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the...

Страница 6: ...ith parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The instrument allows the measure calibration which can...

Страница 7: ...control the evaporator fans Au To control the auxiliary device At To control a silenceable alarm device through a contact that is NO in normal operation then closed when the alarm sounds AL To control...

Страница 8: ...output In the event of a probe error it is possible to set the instru ment so that that the output continues to work in cycles according to the times programmed with parameter rt1 activation time and...

Страница 9: ...the first defrost after power ON can be set with parameter dSd This allows to perform the first defrost to a different interval from ddi time To force the instrument to perform a defrost cycle at eac...

Страница 10: ...y the EP probe is higher than the one set at param eters dtS and also dtE the defrosting is inhibited dtE dts Defrost dF off off off ON ON A B Temp time C NO defrost dde ddi dSd Defrost ddi dSd ddi dS...

Страница 11: ...change Remember that the fans functioning can be conditioned by the Door open function by the digital input 5 10 Alarm functions The alarm conditions of the instrument are Probe errors E1 E1 E2 E2 and...

Страница 12: ...ON Hi Lo Pr1 or they assume the values SP AHA and SP ALA if the alarms are relative AAy 2 4 6 8 AHA SP ALA off off off ON ON Hi Lo AL AAd AAd Temp time Pr1 The maximum and minimum temperature alarms c...

Страница 13: ...ment are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info pleas...

Страница 14: ...r 2 Open Door with Fan Lock 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 9 Defros...

Страница 15: ...1 59 s 1 99 min 10 41 Ftn Fan time activation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59...

Страница 16: ...bled 1 Active for alarms only 2 Active for key pressed only 3 Active for alarms and key pressed oF 65 oFo Auxiliary output function oF Function disabled 1 Control output ot delayed 2 Manual activation...

Страница 17: ...ults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10 AC...

Страница 18: ...e NTC 103AT11 11 INSTRUMENT ORDERING CODE a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R Out1 Relay SPST NO 30A AC1 for resistive l...

Страница 19: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 19...

Страница 20: ...Ascon Tecnologic e33 OPERATING INSTRUCTIONS PAG 20...

Отзывы: