Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 5

4.3 

Electrical connections

Carry out the electrical wiring by connecting only one wire to 
each terminal, according to the following diagram, checking 
that the power supply is the same as that indicated on the 
instrument and that the load current absorption is no higher 
than the maximum electricity current permitted.
As the instrument is built-in equipment with permanent con-
nection inside housing, it is not equipped with either switches 
or internal devices to protect against current overloads: the 
installation will include an overload protection and a two-
phase circuit-breaker, placed as near as possible to the in-
strument and located in a position that can easily be reached 
by the user and marked as instrument disconnecting device 
which interrupts the power supply to the equipment
It is also recommended that the supply of all the electrical cir-
cuits connected to the instrument must be protect properly, us-
ing devices (ex. fuses) proportionate to the circulating currents.
It is strongly recommended that cables with proper insulation, 
according to the working voltages and temperatures, be used.
Furthermore, the input cable of the probe has to be kept sepa-
rate from line voltage wiring.  If the input cable of the probe is 
screened, it has to be connected to the ground at only one side.
Whether the instrument is a 12 V version (Power supply code 
F) it is recommended to use an external TCTR transformer, or 
with equivalent features (class II insulation) and to use only one 
transformer for each instrument because there is no insulation 
between supply and input

D

D

We recommend that a check should be made that the 
parameters are those desired and that the application 
functions correctly 

before connecting the outputs to 

the actuators

 so as to avoid malfunctioning that may 

cause irregularities in the plant that could cause dam-
age to people, things or animals.

4.3.1 

Electrical wiring diagram

(12 A max. for models with removable terminals)

16 FLA

96 LRA

15 A Res.

EN

30 (15) A

61810

Out (H):

15 (15) A

5 FLA

30 LRA

12 A Res.

16 (9) A

Out (R, S):

10 (4) A

60730

EN

UL

Supply

1

3

2

4

6

5

7

9

8

10

12

11

INPUTS

OUT

Pr1

Digital
Input

Pr2

Internal

Buzzer

SPST-NO

NO

NO

C

SPDT

NO

NO

NC

C

5.  FUNCTIONS

5.1 

ON/Stand-by function

Once powered the instrument can assume 2 different condi-
tions:

ON

:  Means that the controller uses the control functions.

STAND-BY:  

Means that the controller uses no control function and 
the display is turned off except for the Stand-by LED.

The transition between Standby and ON is equivalent to 
power ON the instrument providing the electrical power
In case of power failure, the system always sets itself in the 
condition it was in before the black-out
The ON/Stand-by function can be selected:

 

With the key 

/

 pressed for 1 s if 

tUF

 = 

3

;

 

With the key 

/Aux

 pressed for 1 s if 

tfb

 = 

3

;

 

Using the Digital Input if parameter 

iFi

 = 

7

;

5.2 

Normal and economic operation

This tool allows to pre-set two different Setpoints, one 

Nor-

mal

 - 

SP

 and one 

Economic

 - 

SPE

.

Associated with each Setpoint there is the relative differential 
(hysteresis): 

Normal

 - 

rd

 and 

Economic

 - 

rEd

.

Switching between the two modes can be 

automatic

 or 

manual

.

5.2.1 

Normal/Economic operation selection

This function can be used when you need to switch two func-
tional temperatures (eg. Day/Night or week-day/week-end).  The 
Normal/Economic operation can be selected in manual mode:

 

With the key 

/

 pressed for 1 s if 

tUF

 = 

2

;

 

With the key 

/Aux

 pressed for 1 s if 

tFb

 = 

2

;

 

Using the Digital Input if parameter 

iFi

 = 

6

.

The Normal/Economic operation can be selected in auto-
matic mode:

 

Elapsed the 

iEt

 time after the door has been closed 

(Normal/Eco switching).

 

At door opening if the 

SPE

 Setpoint is activated by 

iEt

 

parameter (Eco/Normal switching).

 

Elapsed the 

itt

 time after the door has been closed and 

from the activation of 

SPE

 Setpoint by 

iEt

 parameter 

(Eco/Normal switching).

To use this function, it is necessary to set the Digital Input as: 

iFi

 = 

1

2

 or 

3

.

If 

iEt

 = 

oF

 the selection of Eco/Normal modes via the digital 

input is disabled.
If 

itt

 = 

oF

 the time-out switching from Eco to Normal mode 

is disabled.
Switching to Economic mode is indicated by the label 

Eco

.  

When 

idS

 = 

Ec

 the Economic mode is pointed out with a 

fixed 

Eco

 label otherwise the label 

Eco

 appears every 10 s 

alternated to the display set with parameter 

idS

.

The normal Set Point 

SP

 can be set to a value between the 

one set with parameter 

SLS

 and the one set with parameter 

SHS

 while the Economic Set Point 

SPE

 can be set to a value 

between the one set with parameter 

SP

 and the one set with 

parameter 

SHS

.

Содержание e31 Series

Страница 1: ...ypically used in cooling ap plications with ON OFF temperature control and defrost control with intervals time by stopping compressor The instrument has 1 relay output and 2 NTC temperature probes inp...

Страница 2: ...PROGRAMMING 2 1 Fast Set point programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it...

Страница 3: ...is protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ternal Buzzer SPST NO NO NO C SPDT NO NO NC C 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different condi tions ON Means that the controller uses the control function...

Страница 6: ...The digital input function is defined using the iFi parameter and the action is delayed for the time programmed with pa rameter iti The iFi parameter can be configured for the following functions 0 D...

Страница 7: ...n All these functions are disabled if the relative parameters are set to OFF oF 5 7 Defrost control The automatic defrost control is made with the stopping compressor method it occurs by interval time...

Страница 8: ...rms delay activation time Tempera ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the re...

Страница 9: ...ent are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please...

Страница 10: ...Do not use HC Do not use C3 Do not use C 21 ddL Display Lock during defrost oF Not active on Active at last measure Lb Active with label dEF during defrost and PdF at defrost oF 22 dcd Defrost activat...

Страница 11: ...scon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characte...

Страница 12: ...2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Relay output SPST NO 30A AC1 resistive load R Relay output SPST NO 16A AC1 resist...

Отзывы: