Page 1 of 3

50 Hanover Road, Florham Park, New Jersey 07932    www.ascovalve.com

All Rights Reserved.

E188413

Installation & Maintenance Instructions

SERIES

8320

BRASS OR STAINLESS STEEL CONSTRUCTION

I&M No.V7569

3-WAY NORMALLY CLOSED DIRECT MOUNTED SOLENOID VALVES

FOR NAMUR ACTUATORS Ċ 1/4

I

 NPT Ċ AIR OR INERT GAS SERVICE

NOTICE:    See  separate  solenoid  installation  and  maintenance

instructions for information on:  Wiring, Solenoid Temperature,

Causes of Improper Operation and Coil or Solenoid Replacement.

DESCRIPTION

Series  8320  valves  are  3-way  normally  closed  direct  mounted

solenoid valves designed for air or inert gas service.  Valves are

made of  rugged brass or stainless steel.  Series 8320 valves are

provided  with  a  general  purpose  solenoid  enclosure.    Series

EE8320 is the same as Series 8320 except it is provided with a Class

I, Division 2 explosionproof/watertight solenoid enclosure.

OPERATION

Normally Closed 

(Pressure at Port 1)

Solenoid De-energized:  

Flow  is  from  Port 2 to Port 3.  Port 1 is

closed.

Solenoid Energized:  

Flow is from Port 1 to Port 2.  Port 3 is closed.

Breather Function:

  Allows for spring side of a spring return actuator to

vent at all times through valve exhaust port 3.  

IMPORTANT:  Because

of the breather function, the use of a metering / flow control device at

exhaust port 3 (to control actuator speed) is not recommended.
NOTICE: No minimum operating pressure differential required. 

SOLENOID

DE-ENERGIZED

SOLENOID

ENERGIZED

FLOW  DIAGRAMS

1

2

3

1

2

3

Manual Operation

Manual  operator  (optional  feature)  allows  manual  operation when

desired or during an electrical power outage.  Depending upon valve

requirements,  two types of manual operators are available:

Momentary Push Type (Suffix MO) Manual Operator

To engage push type manual operator, push stem at base of valve body

upward as far as possible.  Valve will now be in the same position as

when  the  solenoid  is  energized.    To  disengage  manual  operator,

release stem.  Manual operator will return to original position.

Maintained Screw Type (Suffix MS) Manual Operator

To engage screw type manual operator, turn red knob clockwise until

it hits a stop.  Valve will now be in the same position as when solenoid

is energized.  Rotate knob fully counterclockwise to disengage.

    CAUTION:    For  valve  to  operate  electrically,  manual

operator must be fully disengaged.

INSTALLATION

Check  nameplate  for  correct  catalog  number,  pressure,  voltage,

frequency, and service.  Never apply incompatible fluids or exceed

pressure rating of the valve.  Installation and valve maintenance to be

performed by qualified personnel.

Future Service Considerations

Provision  should  be  made  for  performing  seat  leakage,  external

leakage,  and  operational  tests  on  the  valve  with  a  nonhazardous,

noncombustible fluid after disassembly and reassembly.

Temperature Limitations

See separate solenoid Installation and Maintenance Instructions  for

maximum  ambient  temperature        Maximum  fluid  temperature  is

180

_

F (82

_

C)

Positioning

Valve may be mounted in any position.

Mounting Solenoid Valve to NAMUR Actuator

Valves are supplied with a hardware kit containing two port gaskets

and three sets of mounting screws; sizes: M5, .190-24 UNC-2A and

.190-32  UNF-2A.    Align  port  2  and  3  port  gaskets  and  solenoid

valve on actuator.  Then install two hex head screws in offset center

holes on either side.  Hand thread screws a  few turns into actuator.

Then tighten screws evenly using a 5/16

I

 

or 8 mm wrench.

Figure 1.  Mounting Dimensions

1.26

[32]

.95

[24]

2 mounting holes

locating hole

port gaskets (2)

3

2

Piping

Apply pipe compound sparingly to male pipe threads only.  If applied

to  valve  threads  the  compound  may  enter  the  valve  and  cause

operational difficulty.  Avoid pipe strain by properly supporting and

aligning  piping.    When  tightening  the  pipe,  do  not  use  valve  or

solenoid as a lever.  Locate wrenches applied to valve body or piping

as close as possible to connection point.
NOTE:    The  exhaust  and/or  pressure  lines  may  be  restricted  to

control actuator speed.

  CAUTION: To protect the solenoid valve, install a strainer

or filter, suitable for the service involved, in the inlet side as

close to the valve as possible.  Clean periodically depending

on service conditions.  See ASCO Series 8600, 8601, and 8602

for strainers.