Asami AMV5-22CC Скачать руководство пользователя страница 1

Owner's Manual 

Original Instructions 

Commercial Air Conditioners 

Multi Variable Air Conditioners 

Compact Cassette Type Indoor Unit 

Models: 

AMV5-22CC

 

AMV5-28CC

 

AMV5-36CC

 

AMV5-45CC

 

AMV5-50CC

 

AMV5-56CC

   

Содержание AMV5-22CC

Страница 1: ...Owner s Manual Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners Compact Cassette Type Indoor Unit Models AMV5 22CC AMV5 28CC AMV5 36CC AMV5 45CC AMV5 50CC AMV5 56CC...

Страница 2: ...perly select the model according to actual using environment otherwise it may impact the using convenience 4 This product has gone through strict inspection and operational test before leaving the fac...

Страница 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Страница 4: ...allation and Drainage System Testing 10 4 4 Panel Installation 13 4 5 Installation of Wired Controller 15 5 Wiring Work 15 5 1 Connection of Wire and Patch Board Terminal 16 5 2 Power Cord Connection...

Страница 5: ...fore starting up or checking the machine Installation should be performed by dealer or qualified technicians Do not install the product by yourself Improper installation may result in water leakage el...

Страница 6: ...hock or personal injury Do not spray water on the air conditioner or it will cause malfunction or electric shock Do not expose the air conditioner directly to water or place it in a damp or corrosive...

Страница 7: ...osal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was...

Страница 8: ...ge 8 Paper pattern for installation 1 Locate the drill hole on ceiling 9 Tapping screw with washer 4 Fix paper pattern 10 Remote controller 1 2 To control the indoor unit 11 Washer fixing plate 4 Prev...

Страница 9: ...NOTES The unit shall be installed in accordance with national standards or local regulations Only qualified personnel can carry out installation work please contact with local dealer before installat...

Страница 10: ...Communication Cable between Indoor Unit and Indoor Outdoor Unit Wire size mm2 Material Standard Remarks Light Ordinary polyvinyl chloride sheathed cord 60227 IEC 52 60227 IEC 53 L 1000 2 0 75 IEC 602...

Страница 11: ...mm2 Minimum Sectional Area of Power Cord mm2 AMV5 22CC 220 240V 1ph 50Hz 208 230V 1ph 60Hz 6 1 1 AMV5 28CC 6 1 1 AMV5 36CC 6 1 1 AMV5 45CC 6 1 1 AMV5 50CC 6 1 1 AMV5 56CC 6 1 1 4 Installation Instruc...

Страница 12: ...height of the unit bolts are field supplied Fig 4 1 4 2 Install the indoor unit temporarily Assemble suspension bolt on the expansion bolt attach the hanger bracket to the suspension bolt Be sure to...

Страница 13: ...flaring port of copper pipe at the center of screwed joint and then tighten the flaring nut with hand as shown in Fig 4 2 2 Use a torque wrench to tighten up the flaring nut until the wrench gives ou...

Страница 14: ...ing fig and arrange insulation to the drainage pipe Improper installation may lead to water leakage and damp the furniture and other things in the room 7 You can buy normal hard PVC pipe used as the d...

Страница 15: ...t be connected to vertical pipe in the same level please select the connection way as shown in following fig No 1 Three way connection of drainage pipe joints Fig 4 3 2 2 No 2 Connection of downspout...

Страница 16: ...odel A B C AMV5 22CC AMV5 28CC AMV5 36CC AMV5 45CC AMV5 50CC AMV5 56CC 170 1030 980 11 During the installation distance from soft drain pipe to the gasket is C when the bolt is tightened It is not all...

Страница 17: ...matically Check if the water pump drains normally through drainage port The water pump will stop automatically after running for 10mins 2 During the test please carefully check the drainage joint make...

Страница 18: ...nd fittings on the same corner as shown in Fig 4 4 4 Fig 4 4 4 2 Temporality hang the panel to body there is four hangers on each corner of the panel hang the hangers to corresponding hooks on the bod...

Страница 19: ...curely or it may cause electric shock Please carefully read the nameplate and the wiring diagram before carry out the wiring work incorrect wiring could cause malfunction or even damage the unit The c...

Страница 20: ...from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III conditions and these means must be incorporated in the fixed wiring in acc...

Страница 21: ...operation all indoor units connected to the same outdoor unit system must be kept energized status Otherwise the unit can t operate normally Fig 5 2 For units with single phase power supply 1 Detach...

Страница 22: ...ance should be connected in parallel between terminal screw D1 and D2 as shown in Fig 5 3 2 5 4 Connection of Communication Wire for Wired Controller 1 Detach the electric box cover 2 Let the communic...

Страница 23: ...One wired controller can control 16 indoor units in maximum at the same time As shown in Fig 5 5 top using it immediately and contact local service center for assistance NOTES The type of indoor units...

Страница 24: ...Multi Variable Air Conditioners Compact Cassette Type Indoor Unit 20 Fig 5 5...

Страница 25: ...oor unit are blocked 2 Check if the grounding wire is in good condition 3 Check if all the power cord and communication cable are securely connected 4 Check if any error code displayed after energized...

Страница 26: ...r a while The inlet or outlet of ODU or IDU is blocked by obstacle Control loop is abnormal Set the unit in cooling mode when outdoor ambient temperature is higher than 43 C Poor cooling effect The fi...

Страница 27: ......

Отзывы: