2.5.
Determining the heat output
There is not a specific rule that enables the calculation of the required heat output. This depends on the amount of
space that is required to be heated and mostly on its insulation. In average the required heat output for a properly
insulated room and with external temperature of 0
ο
C is 40 kCal/h per m
3
.
Taking into account that 1kW equals 860 kCal/h an equivalent of 50W/m
3
can be used. For example, to heat a 150 m3
room (10 x 6 x 2.5m) in an insulated residence, the output required is 150m
3
x 50W/m
3
= 7500W or 7.5 kW.
So, for the main heating, a 10kW appliance is enough.
Indicative combustion
value with efficiency ~80%
Required amount relative
to 1kg dry wood
Fuel
Unit
kCal
kW
Firewood (moisture 15%)
kg
3600
4.2
1.00
Firewood (moisture 50%)
Kg
1850
2.2
1.95
Wood briquettes
Kg
4000
5.0
0.84
Coal briquettes
Kg
4800
5.6
0.75
Coal
Kg
7700
8.9
0.47
Coke
Kg
6780
7.9
0.53
Gas
m
3
7800
9.1
0.46
Diesel
L
8500
9.9
0.42
Electricity
kW/h
860
1.0
4.19
Table 2.5.1
3.
E
NDORSEMENTS AND CERTIFICATIONS
3.1.
Endorsement
The ARTE® fireplace you chose has been tested according to
EN13229
. The declaration of performance (DoP) of each
MENTOR model can be found at the URL of the company for each model.
3.2.
Features marking plate
ARTE® fireplace’s feature marking plate is located on the right side of the appliance
.