Arrowhead Alarm Products HM-SMOKE Скачать руководство пользователя страница 1

Service & Maintenance 

 

Once a month: Press the test button 

to trigger the detector. Note, putting 

the alarm panel in programming mode, 

will prevent the alarm sirens from  
triggering as well. 

 

Every 6 months: Vacuum or blow 

dust out of the detector to help reduce 
false alarms. 

500mm 

500mm 

SL

O

PED RO

OF

 

Min. 

200mm 

Operation & Testing 

During Normal Operation the LED flashes 
every 45 seconds. 

 

Pressing the Test  Button will activate test 

mode, triggering both the Relay and the 
Buzzer. 

 

The smoke alarm will automatically reset 

when all the smoke has cleared. 

 

Hush feature. Whilst the smoke detector is 
in activated, pressing the test button for 1 

second, will silence that smoke detectors 
sounder. 

This will not hush the controllers 

sounders or other smoke detectors connected

 

ARROWHEAD ALARM PRODUCTS Ltd. 

344b Rosedale Rd, 

Albany,  
Auckland. 

Ph. 09 414 0085 

Fax. 09 414 0088 

www.aap.co.nz 

 

 
v2.01 

HM-SMOKE 

AUTO RESETTING SMOKE DETECTOR 

With Power Monitoring 

Specifications 

Detection Type   

Photoelectric Chamber 

Power Source   

9-16 Volts DC 

Standby Current 

25mA 

Alarm Current   

20mA 

Buzzer Output   

85db @ 3 meters 

Output Relay   

N/O and N/C Contacts 

 

 

 

 

100mA max 

Dimensions 

 

Ø

100mm x 55mm 

Standards:                  GB4715-2005, EN14604, UL217

 

Suggested Mounting Locations  

Smoke alarms must be located in escape routes on 
all levels within the household unit.  

On levels containing sleeping spaces, they must be 

installed within the sleeping space, or within  

3 metres of every sleeping space door. And they 

must be audible through closed doors. 

 

Always Refer to NZS 4514:2009 or the latest  

standard for full installation recommendations. 

= MOUNTING AREA 

= DON’T FIT AREA 
  (DEAD AIR SPACE) 

M

ax

. 3

0

0

m

m

 

CEILING 

W

AL

BEST  

LOCATION 

ACCEPTABLE 

LOCATION 

Note. Smoke Detectors should be 

mounted a minimum of 400mm away 

from Air Con. or forced air vents. 

 

Test at least once a month.  

 

 

Min.  

100mm 

Min.  

200mm 

900mm  

or less 

Beams, joists and 
exposed rafters 
deeper than 
460mm are 
treated as walls 

Min.  

200mm 

Always Refer to NZS 4514:2009 or the latest  

standard for full installation recommendations. 