Installation pro
-
cedure (Fig.5)
Carefully examine the installation area, eliminating any danger to the op-
erator
remove the package only if the counter is placed in the area of use.
Step
Action
1
lift the cabinet safely
2
use suitable scissors to cut the clip tightening straps-A-
3
remove the clips and the frame
4
lower and place the cabinet in the area of use
7
adjust the horizontal position of the cabinet using a spirit level (Fig.9)
8
check that all feet are into contact with the floor
9
level the cabinet both in front and back
10 gently remove the protective film, eliminate glue residues with suitable
solvents
11
carry out the first cleaning using neutral products and a soft cloth.
- Install maximum 3 cabinets within the same power supply and cooling
line
- If the cabinet is moved, check its levelling again; incorrect levelling will
compromise the operation of the cabinet.
What to avoid
•
DO NOT use alcohol to clean the methacrylate parts (Plexiglass)
•
DO NOT use abrasives or metal sponges
•
DO NOT install the cabinet (Fig.10):
- in areas at risk of explosion
- in open air and therefore exposed to the elements
- near heat sources (direct sunlight, heating systems, incandescence
lamps, etc.)
- in the vicinity of air currents (close to doors, windows, air-condition-
ing systems, etc.) that exceed a speed of 0.2 m/s
•
Dragging. Failure/deformations/tearing
DO NOT
drag/push the cabinet
Follow the instructions for safe handling.
i
For correct disposal, the package consists of:
wood - polystyrene - polythene - PVC - cardboard.
14.
Electrical connection
DANGER! Live parts. Electrocution.
REMOVE THE ELECTRIC POWER SUPPLY BEFORE ANY OPERATION!
Ensure that the casing does not come into contact with the electrical panel.
Provide a suitable grounding system!
i
The systems must be set up in accordance to the regulations that regulate manufacture,
installation, use, and maintenance foreseen by the norms in force in the country where the
refrigeration system is installed.
To ensure normal operation, the maximum voltage variation must be /- 6% of the
nominal value.