Armstrong h-53 Скачать руководство пользователя страница 2

installation &   

operating instructions

In-line circulating 

pumps

2

115V

 or 

208-230V

 

1

ph wiring - see 

Appendix 

1

 for more details

5.0  speed setting

The 

ecm

 motor operates in speed mode when connected to the 

pump. You can adjust the demand of the motor manually using 
the 

hmi

 Interface. The motor information and error code are 

displayed in the Interface. 
All interface details and future explanation can be seen in 
Appendix 

1

.

6.0  0v to 10v dc control

0

to

 

10V DC 

control is available where the system allow, using 

an external source and wiring. This input is for a linear closed-
loop speed control and a speed signal for speed monitoring, 
which can greatly save on Energy consumption.
For more details please see Appendix 

1

.

7.0 lubrication

caution 

Do not put oil in the 

maintenance free

 circulators. 

These models contain MF in their item numbers and 
are labelled: 

this bearing assembly contains perma-

nently lubricated bearings and does not need any 
oiling or greasing

.

Stop motor before lubricating, do not over-oil or spill oil on 
resilient motor rings. Do not force oil into cups, and stop if cup 
fills before addition of specified amount.

Pump lubrication

Only applicable for pumps those are with sleeve bearing 

sba

 

and have oil cup for lubrication.

Immediately after pump is installed and before 
running, slowly add the oil (

sae 30

 non-detergent 

regular, supplied with pump) to pump oil cup, located  

on top of bearing bracket:

s69, h63

 to

 h67

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

 oz.

At the start of each following heating season, lubricate with 

sae 30

 oil. Lubricate every six months for high temperature or 

constant operation. Be sure oil is visible at the top and center of 
window on side of bracket and maintain this level at all times.

Motor lubrication

caution

Stop motor before lubricating. Do not over-oil or spill 
oil on resilient motor rings.

This motor has been lubricated properly at the factory. At  
the start of each following heating season, however, on motors 
with oil cups, add 

15

 drops 

sae 30

 non-detergent oil to each 

motor cup.
If the motor is fitted with grease fittings, follow the motor 
manufacturer's recommended procedure. Motors without oil 
cups or grease fittings are custom-greased for several years 
operation and require little or no attention.

8.0  seal replacement

Remove the pump bracket from the body. Remove the impeller, 
damaged seal assembly, ceramic insert and rubber cup. Clean 
the recess in bearing bracket cover plate and install a new re-
tainer cup and ceramic insert. Check the condition of the shaft 
sleeve. If scored, replace the shaft assembly. Otherwise, clean 
shaft extension and polish sleeve with a fine crocus cloth, using 
a rotating motion, if required.
Press against the coupler end of the shaft to take up play while 
pressing new seal firmly against the stationary face. A slight 
amount of clean vaseline may be put on shaft sleeve to assist 
installation. Press down firmly and evenly, using two screw-
drivers and pushing against the four ears of driving band (the 
metal ring around rubber bellows), or around top outer edge of 
driving band on models 

s53

s57

 and

 h53

h54

.

Continue pressing against coupler end of shaft, re-mount 
impeller and re-assemble the seal bearing assembly into body. 
If necessary, install a new body gasket and clean gasket surface 
of both volute and bracket.

connections

green/verde screw

ground

Содержание h-53

Страница 1: ...nstalled on the discharge and suction side of the pump to facilitate service On larger pump sizes a check valve should be located on the discharge side of pump between the pump body and the gate valve to prevent damage due to water hammer 2 0 system cleanliness Before starting the pump the system must be thoroughly cleaned flushed and drained then replenished with clean liquid Welding slag and oth...

Страница 2: ...perature or constant operation Be sure oil is visible at the top and center of window on side of bracket and maintain this level at all times Motor lubrication caution Stop motor before lubricating Do not over oil or spill oil on resilient motor rings This motor has been lubricated properly at the factory At the start of each following heating season however on motors with oil cups add 15 drops sa...

Страница 3: ...tion with and adherence to the National Electrical Code nec and National Fire Protection Association nfpa standards and to local codes are required It is important to observe safety precautions to protect personnel from possible injury Person nel should be instructed for handling each of the following Insulate all connections carefully to prevent grounding or short circuits Reinstall all conduit a...

Страница 4: ...rface board communicates with the motor control to operate the motor in speed mode The operating parameters are programmed in the eeprom of the motor control not the PerfectSpeed User Interface On power up the interface board extracts the operating parameters from the motor control Parameter categories include Motor direction Motor mode of operation Motor output display Motor profile PerfectSpeed ...

Страница 5: ...ethods of setting the Input Demand See Table 3 for definitions of the two options Table 4 Setting input demands options set with on board potentiometer set with 0 V to 10V DC control signal AC line connections Check to see if the line voltage matches the nameplate voltage connections green verde screw ground Configuration scenarios This section provides examples of different configurations and bri...

Страница 6: ...t running If the PerfectSpeed motor with User Interface isn t running perform the following checks 1 Ensure that both the PerfectSpeed motor and User Inter face have proper line voltage for intended application 2 Turn the User Interface on board potentiometer fully clock wise 100 demand and check to see if the motor runs 3 If 0V to 10V DC input is in use disconnect the external input from the User...

Страница 7: ...ains definitions for acronyms and terms oc curring in the Operation Configuration and Troubleshooting Manual or in the PerfectSpeed User Interface ccw Counter clockwise direction Motor rotation is viewed from the lead end of the motor not the shaft cw Clockwise direction Motor rotation is viewed from the lead end of the motor not the shaft dE Demand The set point of the motor ecm Electronically Co...

Страница 8: ...fined by the maximum operating parameters Also called motor slew rate Motor Speed Limit A user defined limit in rpm equating to 100 demand in Speed Mode of Operation Motor Power Limit A user defined limit in Watts of output power The parameter cannot be less than 25 of the value in the Motor Table Refer to Appendix A Motor Charts Motor Torque Limit A user defined limit in lb in equating to 100 dem...

Страница 9: ...installation operating instructions In line circulating pumps 9 ...

Страница 10: ...hester united kingdom m11 2et 44 0 8444 145 145 93 east avenue north tonawanda new york u s a 14120 6594 1 716 693 8813 23 bertrand avenue toronto ontario canada m1l 2p3 1 416 755 2291 unit 903 888 north sichuan rd hongkou district shanghai china 200085 86 0 21 5237 0909 rua josé semião rodrigues agostinho 1370 galpão 6 embu das artes sao paulo brazil 55 11 4781 5500 b i r m i n g h a m heywood wh...

Отзывы: