English Data-interface
M
OUNTING THE UNIT
Mount the unit via screws or bolts through the four mounting holes in the base.
Ensure the unit is mounted on a flat, solid, vertical surface such that the base
will not flex or warp when the mounting screws/bolts are tightened.
C
ONNECTING THE DATA GATHERING PANEL TO A CONTROL PANEL
Refer to the control panel installation guide for instructions.
C
ONNECTIONS
: 5
MM PLUG ON SCREW TERMINALS
(
FIGURE
➊
)
Power
Connection of the 23 Vac, AC from the transformer.
Earth
Earth wires from all pieces of equipment must be earthed at
one system earth. For further detail see the ATS control panel
installation guide.
Note
Power and battery wires should be firmly tied in order to avoid
short circuits to any other part of the system in case a
connection of the wire is broken.
Batt
+ - connections to a 12V/6.5AH maximum sealed lead acid
battery.
AUX PWR
12Vdc auxiliary power output to supply detector, etc. 700mA
maximum current.
J2
DATABUS
Data +, Data - and common 0V connection to the system
databus. Remote units can be up to 1.5 km from the control
panel. Also see the control panel installation guide.
J2
TAMPER
Connection for panel tamper switches. Can only be used with
normally closed contacts such as the panel tamper switches.
①
Normally closed front panel tamper contact
②
Normally closed rear panel tamper contact
J4 J6 J7
③
④
Zones 1 to 8 require 4k7 end-of-line resistors for normal state.
J7 –
SIREN
Positive and negative connection to external 8 Ohm siren
speaker. 1k resistor must be fitted across these terminals if
the siren is not connected. The siren output is the 16th (last)
output allocated to the DGP address. e.g. on DGP 1 the siren
is output 32. On DGP 2 the siren is output 48, etc.
LED’
S
RX
LED flashes to indicate polling data is being received on the
system databus from the ATS control panel. If the LED does
not flash the control panel is not operational or the databus is
faulty (usually cabling).
TX
LED flashes to indicate the DGP is replying to polling from the
ATS control panel; If the RX LED flashes but the TX LED
does not, it indicates that the DGP) is nor programmed to be
polled in the control panel or is not addressed correctly.
Z
ONE AND OUTPUT NUMBERING
Control panel
1 – 16
DGP8
129 - 144
DGP1
17 - 32
DGP9
145 -
160
DGP2
33 - 48
DGP10
161 -
176
DGP3
49 - 64
DGP11
177 -
192
DGP4
65 - 80
DGP12
193 -
208
DGP5
81 - 96
DGP13
209 -
224
DGP6
97 -
112
DGP14
225 -
240
DGP7
113 - 128
DGP15
241 - 256
O
UTPUT NUMBERING
A DGP can have a maximum of 16 outputs available as relays or open
collectors outputs. The output numbers are the same as the 16 zone numbers
allocated to the DGP address.
Z
ONE NUMBERING
The ATS 1201 has 8 zones that can be expanded using the ATS 1202 (8
zones) to a maximum of 32 zones. If the number of zones exceeds 16, then the
zones are taken from the next DGP address and DGP ceases to exist.
e.g. DGP 1 has 24 zones (zones 17 to 40). The next DGP in the system must
now be addressed and polled as DGP 3, because zones 33 to 40 on DGP 1
have taken from DGP 2.
The unused zone numbers in the system (zones 41 to 48) must be
programmed in the zone database as Type 0.
C
ONNECTIONS
:
HEADERS AND SOCKETS
J5 –
E
XT I
/
PS
Connection to ATS1202 8-zone expansion cards via 10-way
cable supplied with the expander card. Set dipswitch A of the
DGP to ON if two or three expansion cards are connected.
Dipswitches 1 to 3 on the expansion card are used to identify
the expander number. See the ATS1202 installation guide for
details.
J8
-
OUTPUTS
+12Vdc supply and open collector or data output for
connection to ATS 1810, ATS 1811 and ATS 1820 output
cards via 10-way cable supplied with the output card. Up to
sixteen outputs are available with 8-way relay or 16-way open
collector cards, (4-way and 8/16-way output cards cannot be
used together on the same DGP).
L
INKS
T
ERM
Refer to the control panel installation guide.
TST
3
Disable mains fail monitoring.
E
ARTH
, +12V
⑤
⑥
DGP
DIPSWITCH SETTINGS
1 - 4 Address setting. Set switches 1 - 4 to OFF to disable the DGP. See
also figure for correct address settings.
A
ON - DGP has 2 or 3 ATS1202 zone expanders connected to J5.
OFF - DGP has none or only 1 ATS1202 connected to J5.
B
ON - ATS1811 8-way relay card or ATS1820 16-way open collector
card connected to J8.
OFF - no ATS1811 or ATS1820 connected to J8. Use this setting also
if an ATS1810 is connected to J8.
CD
OFF – Not used.
O
VER
-
CURRENT PROTECTION
F1
1 A fuse to limit “Aux” O/P current. (
AUX PWR
and
SIREN
).
F2
3 A fuse to limit current when unit is running on the battery.
C
ONNECTING THE MAINS POWER
Use the mains connector terminal for connecting the mains power supply. A
fixed or flexible mains lead to an earthed mains outlet can be used.
IMPORTANT: Disconnect the mains power before opening the cabinet!
1