Aritech ATS 500A Series Скачать руководство пользователя страница 12

 

12 / 18 

 

P/N 466-

5570 (EN) • REV E • ISS 22MAR22 

Battery capacity, Ah 

12 

18 

25 

36 

Applicable housing 

LM 

MM+, 
LM 

LM 

LM 

Security 
approval / Grade 

Discharge 
time, h 

Charge 
time, h 

Auxiliary current, mA 

NF&A2P Grade 2 
(EN+RTC) 

36 

72 

180  350 

540 

850 

NF&A2P Grade 3 
(EN+RTC), VdS-C 

60 

24 

— 

150 

260 

450 

Note: 

18 Ah battery blocks some entry holes in the MM 

housing. 

Example for ATS1500A(-IP) EN Grade 2 

When using battery backup as specified for EN Grade 2 using 
a 12 Ah battery, the maximum available auxiliary current is 
750 mA. 

Example for ATS3500A(-IP) EN Grade 3 

When using battery backup as specified for EN Grade 3 using 
an 18 Ah battery, the maximum available auxiliary current is 
450 mA. 

This current is the max grand total available current that may 
be used for auxiliary components such as:  

• 

Devices on the Advisor Advanced system databus 

• 

Detectors on the auxiliary power output 

• 

Communication devices via MI-bus (e.g. GSM, IP) 

Temporary used current such as: Sirens and Strobes are not 
included. 

Fuse rating must be taken into account. 

Battery status information 

Various detection ways are provided to understand the status 
of a battery. 

A short battery test will be applied to detect following within 
10 seconds: 

• 

Battery fail (or battery missing) to inform installer no 
battery is attached or a poor battery is attached. Event will 
be logged and notified. 

• 

Low battery as soon as battery becomes below 
10.5 V with or without mains. Event will be logged, notified 
and reported. 

Another battery test will be applied once per day to even better 
understand battery status. In case battery wears out a battery 
fail message will be logged, notified and reported. 

System monitoring 

The system provides monitoring for the following items. 

Table 5: Monitored items 

Monitoring 
function 

Message 

Cause 

AC Mains 

Mains fail 

Loss of external power 
supply [1][2] 

Battery 

Battery low 

Battery low voltage [1] 

 

Battery test fail 

Exhausted battery 

Battery charger fail 

 

Fuse/power output fail 

Output overload 

Monitoring 
function 

Message 

Cause 

Power outputs 

Fuse/power output fail 

Exhausted fuse 

Fuse loss 

Short circuit 

Overload 

Power supply 

Power unit/power 
output fail 

Power unit failure 

Overvoltage 

Tampers 

Device tamper 

Device sabotage 

[1]  Mains fail and Battery low will finally result in Battery deep 

discharge protection. 

[2]  Mains fault message is indicated in case of AC trouble or PSU 

fault. View the panel event log to identify the fault source. 

Regulations 

This section describes settings and actions required by 
particular regulations and norms. 

EN 50131 Grade 2 

The following options and values are mandatory for EN 50131-
1 Grade 2 regulations. 

• 

1.2.6.n.3 

Period, see “Transmitter polling interval 

requirements” on page 353. 

• 

2.2.1.n.3.4 View areas and 2.2.1.n.3.6 Control areas 
settings are identical 

• 

2.2.1.n.3.11 Buzzer silent, never 

• 

2.2.1.n.3.12 Quick set, off 

• 

2.2.1.n.3.13 Function keys, all set to None 

• 

2.2.1.n.3.18 ACK on keypad, set to None for non-LCD 
keypads 

• 

3.1.n.7.3 SMS control, disabled for all users 

• 

3.2.n.6 User group options, 25. No OP/CL reports option 
set to No 

• 

4.1.n.6.1 Inhibit, set to No for all zones with type 5. Panic, 
6. 24H 

• 

4.1.n.6.6 Swinger shunt, set to Yes for all zones 

• 

4.1.n.6.26 ACK on keypad, set to None for all zones with 
type 9. Keyswitch 

• 

4.2.n.3 Entry time, 45 s maximum 

• 

4.2.n.5.1 Entry alarms, Instant 

• 

7.2.n.2 Active, set to No for all schedules. 

• 

8.1.2.1 Activation, external siren 90 to 900 s 

• 

8.1.2.2 Delay time, external siren 600 s maximum 

• 

8.1.3.1 

Armed display, set to 00’00 

• 

8.1.3.4 Mains reporting delay, 3600 s maximum 

• 

8.2.1 User code required, enabled 

• 

8.3.1 Armed display, always 

• 

8.3.3 Alarm list, disabled 

• 

8.4.1 RTS options, all enabled except zone technical 
alarm, which is optional 

• 

8.4.2 Inhibit includes, all allowed except engineer reset, 
which must be disabled 

• 

8.4.6 Pending alarms, enable EN50131 

• 

8.4.10 Report exit fault, EE fault 

• 

8.6.4 Swinger shunt 

≥ 3 

• 

8.6.5 Report restore, on ACK 

• 

8.7.8.1 Remote config, No 

• 

8.8.14 Siren report, Fault 

• 

9.3.n.2 Line fault, enabled per path used 

• 

9.3.n.3 Line fault delay, 0 s 

Содержание ATS 500A Series

Страница 1: ...T C 1 C 2 3 C 4 5 C 6 7 C 8 AC BATT LC OUTPUTS HC OUTPUTS SIR TMP AUX POWER INPUTS C T S3 C CON16 NTC COMMS 12V 0V D D 250 250 9 30 61 5 28 2 37 2 125 9 61 5 126 4 118 Ø20 2 1 1 1 1 1 Rx Tx USB MI IP CON12 CON13 T1 T2 S4 S5 S1 C S2 C T C 1 C 2 3 C 4 5 C 6 7 C 8 AC BATT LC OUTPUTS HC OUTPUTS SIR TMP AUX POWER INPUTS C T S3 C CON16 NTC COMMS 12V 0VD D 315 40 385 55 1 1 1 1 1 1 15 109 4 102 5 60 2 60...

Страница 2: ... C 8 AC BATT LC OUTPUTS HC OUTPUTS SIR TMP AUX POWER INPUTS C T S3 C CON16 NTC COMMS 12V 0V D D 259 129 5 73 403 54 5 45 5 73 395 50 5 70 126 5 41 5 70 253 1 1 1 2 Rx Tx USB MI IP CON12 CON13 T1 T2 S4 S5 S1 C S2 C T C 1 C 2 3 C 4 5 C 6 7 C 8 AC BATT LC OUTPUTS HC OUTPUTS SIR TMP AUX POWER INPUTS C T S3 C CON16 NTC COMMS 12V 0VD D 35 315 90 31 33 24 445 35 97 5 157 5 157 5 1 1 1 1 1 2 ...

Страница 3: ...ium MM and MM and large housing LM pry off tamper mount N N Rx Tx USB MI IP CON12 CON13 T1 T2 S4 S5 S1 C S2 C T C 1 C 2 3 C 4 5 C 6 7 C 8 AC BATT LC OUTPUTS HC OUTPUTS SIR TMP AUX POWER INPUTS C T S3 C CON16 NTC COMMS 12V 0V D D 1 1 1 1 1 2 COM NO COM NO C T TAMPER B C D E A MM MM LM ...

Страница 4: ...shielding B A 1 2 3 5 6 10 9 22 21 23 18 16 24 25 19 17 15 14 26 4 11 13 Rx Tx USB MI IP CON12 CON13 T1 T2 S4 S5 S1 C S2 C T C 1 C 2 3 C 4 5 C 6 7 C 8 AC BATT LC OUTPUTS HC OUTPUTS SIR TMP AUX POWER INPUTS C T S3 C CON16 NTC COMMS 12V 0V D D 12 20 8 7 1740 ATS1201 E 1740 Advisor Advanced ATS1210 E ATS1135 ATS1203 E 1 2 3 4 5 6 7 3 3 4 4 4 4 5 5 7 7 8 9 8 9 9 ...

Страница 5: ...TS1500A IP MM Metal MM 315 x 388 x 85 5 2 ATS1500A SM Metal SM 250 x 250 x 86 2 8 Model Enclosure Dimensions mm Weight kg ATS1500A IP SM Metal SM 250 x 250 x 86 2 8 ATS1500A LP Plastic LP 257 x 400 x 112 2 6 ATS1500A IP LP Plastic LP 257 x 400 x 112 2 6 ATS3500A MM Metal MM 315 x 388 x 85 5 2 ATS3500A IP MM Metal MM 315 x 388 x 85 5 2 ATS3500A LP Plastic LP 257 x 400 x 112 2 6 ATS3500A IP LP Plast...

Страница 6: ...ons are given in mm For more details on connections and connecting devices to the Advisor Advanced see Cabling on page 8 For details on connecting pry off tampers see Pry off tamper mounting below Pry off tamper mounting For medium MM and MM and large housings LM follow the steps in Figure 6 For large plastic housing LP follow the steps in Figure 7 Caution Once the ATS MM TK tamper assembly has be...

Страница 7: ...at depending on the battery model the connectors can be located differently 5 Mount the battery shield using four screws WARNING The battery shield must be mounted during normal device operation In case a battery BS131 12 V 18 Ah in an ATS1640 housing is used in combination with ATS7700 PSTN expander board it is required to have double insulation in place Use adequately insulated wires for PSTN ca...

Страница 8: ...on may not exceed 30 m For longer distances use relay output expansion for example ATS624 four relay expander The minimum clearance between equipment closures is 50 mm between equipment vents Only use these units in a clean environment and not in humid air Environmental requirements are given in Specifications on page 9 For the panel terminal connections the recommended torque is 0 3 to 0 4 N m Th...

Страница 9: ...e zones However by programming the zones as dual loop all zone inputs can be programmed to give a few states indication for the same zone Depending on the detector model do the following to set up zones Choose your EOL connection type Program input mode Set end of line resistor values Configure anti masking option Refer to Advisor Advanced ATSx500A Installation and Programming Manual for details S...

Страница 10: ...ngs applicable for particular batteries are specified in Auxiliary current and battery capacity on page 11 6 High temperature and multiple charge cycles may greatly reduce battery life time See the specifications for your battery for more information 7 If during a manual or a programmed battery test the battery voltage drops below this threshold the battery test fails 8 Deep discharge protection m...

Страница 11: ...de or minimum air pressure 2000 m above mean sea level Fuses Battery ATS1500A IP ATS3500A IP 2 A resettable ATS4500A IP 3 A resettable 12 V aux 1 A resettable System databus 1 A resettable Siren 1 high current output S1 1 A resettable Siren 2 high current output S2 1 A resettable Siren 3 high current output S3 1 A resettable Mains mains fuse ATS1500A IP SM LP T 160 mA 230 VAC slow Aritech 33 119 A...

Страница 12: ...attery charger fail Fuse power output fail Output overload Monitoring function Message Cause Power outputs Fuse power output fail Exhausted fuse Fuse loss Short circuit Overload Power supply Power unit power output fail Power unit failure Overvoltage Tampers Device tamper Device sabotage 1 Mains fail and Battery low will finally result in Battery deep discharge protection 2 Mains fault message is ...

Страница 13: ...rmed daily The following features are not allowed not evaluated Keyswitch zone types to set and unset the system Presetting indication and any automatic override of set prevention Refer to Table 6 below for all supported options for notification requirements Table 6 EN 50131 1 2006 options Notification equipment Alarm reporting Grade 3 options A B C D Remotely powered audible WD 2 Optional Optiona...

Страница 14: ...vices depending on intrusion panel regardless of type independent of other expanders ATS1201E 8 to 32 zone DGP expander with 3 A PSU small enclosure EN 50131 Grade 3 ATS1204E 8 to 32 zone DGP expander with 3 A PSU large enclosure EN 50131 Grade 3 I O expanders Panel can support up to 3 I O devices depending on the type ATS608 Plug in 8 zone expander ATS624 4 relay board ATS626 16 open collector ou...

Страница 15: ... ATS1451 ATS1452 ATS1455 ATS1457 ATS1458W ATS1458B ATS1459 ATS1482 Wiring and interconnections when used for CPNI applications The use of wiring and the associated interconnections shall be appropriate for the system performance required and the local conditions within the service environment The installation should conform to good working practices and be in accordance with the requirements of th...

Страница 16: ...re also connected to that network they do not prevent or interfere with the correct operation of the alarm transmission system INCERT policy The required settings for INCERT Grade 2 are all EN 50131 Grade 2 required settings and settings for INCERT Grade 3 are all EN 50131 Grade 3 required settings with the following modifications 1 2 9 1 m n 2 Batt test freq Everyday 8 2 1 User code required Enab...

Страница 17: ...500A IP MM is upgradable to Security Grade 3 using the ATS MM TK tamper kit Mode of operation as per EN 50136 2 2013 The transmission of the events to the central station takes place by means of pass through procedures in accordance with EN 50136 2 2013 Tested and certified by VdS Schadenverhütung GmbH Important To comply with the above standards it is required to configure the system according to...

Страница 18: ...18 18 P N 466 5570 EN REV E ISS 22MAR22 ...

Отзывы: