Chapter 3: Configuration and commissioning
1X-E4 Series Installation Manual
37
Fire routing delay
Use this menu to configure a fire routing delay of up to 10 minutes in operating
modes where the feature is available. The default fire routing delay is 1 minute.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at Operator user level.
To enable a configured delay:
1. Exit Installer user level.
2. Enter the Operator user level password.
3. Press the Fire Routing Delay button.
A steady Fire Routing Delay LED indicates that the delay is enabled.
Fire routing delay operation
The delay applies to the activation of fire routing (if configured) only if
all
of the
following are true:
• The delay is enabled
• The initiating device (detector or manual call point) is installed in an automatic
zone (or the initiating device is a detector installed in a mixed zone)
• The initiating device is configured in a zone with delays configured (by
default)
• A fire routing inhibit delay input is not activated (if configured)
• Any input using the
delays off
function must not be active
If the delay is not enabled, the control panel activates fire routing (if configured)
immediately after the detection of the fire alarm.
Содержание 1X-E4 Series
Страница 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Страница 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Страница 84: ...Chapter 5 Technical specifications 78 1X E4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Страница 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...