Chapter 2: Installation
1X-E4 Series Installation Manual
19
Selecting 115 or 230 VAC operation
WARNING:
Electrocution hazard. To avoid personal injury or death from
electrocution, remove all sources of power and allow stored energy to discharge
before installing or removing equipment.
Power switching for 115 or 230 VAC operation is automatic for two- and four-
zone control panels and no configuration is required.
The default power setting is 230 VAC. For 115 VAC operation, use a small
screwdriver to change the power setting switch, located on the side of the power
supply unit, as shown in Figure 11 below.
Caution:
Risk of equipment damage. An incorrect power setting can destroy the
power supply.
Figure 11: Selecting 115 or 230 VAC operation