Chapter 2: Installation
1X-E4 Series Installation Manual
11
Connecting zones and zone devices
Connecting zones
Connect zone wires as shown in Figure 4, Figure 5, Figure 6, and Figure 7
above. Line resistance is shown in Table 3 below.
Table 3: Line resistance
Zone type
Line resistance
Standard and active end-of-line EN 54-13 and intrinsically-safe
Mixed
40 Ω max.
Not supported [1]
Automatic
55 Ω max.
50 Ω max.
Manual
55 Ω max.
50 Ω max.
[1] Mixed zones are not permitted in installations requiring EN 54-13 or intrinsically-safe
configuration.
To measure the line resistance:
1. Create a short circuit at the end of the zone line.
2. Measure the resistance between the positive and negative lines with a
multimeter.
Note:
The default zone detection settings for each operating mode can be found
in Appendix A “Configuration presets” on page 79. To change the zone detection
setting, see “Advanced configuration” on page 40.
Terminating zones
Zone termination is required at all times, whether the zone is used or not. The
type of termination depends on the installation, as shown in Table 4 below.
Table 4: Zone terminations
Installation type
Zone termination
Standard and intrinsically-
safe zones
4.7 kΩ end
-of-line resistor
EN 54-13 zones
EOL-Z end-of-line device (polarity sensitive)
Active EOL
Active end-of-line device
Note:
Unused zones must be terminated with an active end-of-line device or
configured as passive end-of-
line and terminated with a 4.7 kΩ, 5%, 1/4 W end
-
of-line resistor.
Содержание 1X-E4 Series
Страница 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Страница 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Страница 84: ...Chapter 5 Technical specifications 78 1X E4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Страница 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...