WALL-HUNG CONDENSING

GAS BOILER

GENUS PREMIUM

EVO HP 

45/65/85/100/115/150

Installation and Servicing Instructions

Содержание GENUS PREMIUM EVO HP 100

Страница 1: ...GENUS PREMIUM EVO HP WALL HUNG CONDENSING GAS BOILER GENUS PREMIUM EVO HP 45 65 85 100 115 150 Installation and Servicing Instructions...

Страница 2: ...e gas exhaust duct lengths 18 Type of air suction flue gas exhaust ducting 18 Electrical connection 19 Peripheral unit connection 19 Electrical diagram 45 65 20 Electrical diagram 85 100 21 Electrical...

Страница 3: ...s not the case please contact your supplier Keep all packaging material clips plastic bags polystyrene foam etc out of reach of children as it may present a potential hazard In the event of a fault an...

Страница 4: ...the ladder and parapets on the landing Personal injury caused by falling from a height During all work carried out at a certain height generally with a difference in height of more than two metres mak...

Страница 5: ...t temperature XX C D H W operation set D H W set temperature active with indirect cylinder connected XX C D H W operation active D H W set temperature active with indirect cylinder connected XX C Exte...

Страница 6: ...product description 6 Overall wiew GENUS PREMIUM EVO HP 85 100 GENUS PREMIUM EVO HP 45 65 1 2 3 4 5 6 7 A C E 9 10 11 13 16 12 14 15 8 A C E 1 2 4 6 17 17 8 10 5 16 12 7 14 15...

Страница 7: ...glass 4 Ignition electrode 5 Ignitor 6 Modulating fan 7 Minimum water pressure switch 8 Siphon 9 Circulation pump with air release valve 10 Mixer 11 Silencer 12 Gas valve 13 Detection electrode 14 C...

Страница 8: ...81 81 162 140 232 25 586 54 74 75 123 A C E F A C E F Overall Dimensions A Central Heating Flow 1 M C Gas Inlet M E Central Heating Return 1 M F Condesate discharge A Central Heating Flow 1 M C Gas In...

Страница 9: ...uct description 9 A Central Heating Flow 1 1 2 M C Gas Inlet 1 M E Central Heating Return 1 1 2 M 465 888 81 81 162 97 54 74 123 75 140 231 26 586 115 696 150 A C E F A C E F GENUS PREMIUM EVO HP 115...

Страница 10: ...24 0 25 0 25 Loss of burner gas when operating 2 8 2 8 2 8 2 8 EMISSIONS Available air pressure Pa 130 150 140 140 NOx class Less than 70 mg kWh class 5 5 5 5 Flue gas temperature G20 80 C 60 C C 67 6...

Страница 11: ...band Loss when stopped T 50 C 0 15 0 15 Loss of burner gas when operating 3 2 3 1 EMISSIONS Available air pressure Pa 180 200 NOx class Less than 70 mg kWh class 5 5 Flue gas temperature G20 80 C 60 C...

Страница 12: ...m other appliances unless the flue is meant to serve more than one user in accordance with current legal requirements Where there is already a connection to existing flue exhausts check that these exh...

Страница 13: ...he supplied gas corresponds to the type of gas for which the boiler was designed see the data plate located on the appliance itself It is also important to check that the pressure of the gas methane o...

Страница 14: ...ure device outlet must be connected to a drainage siphon which can be checked visually in order to prevent maintenance procedures causing harm to people animals or property the manufacturer shall not...

Страница 15: ...n the system is frequently refilled with water In such cases if the system is then partially or totally drained it must be refilled using treated water again Discharge of condensation High energy effi...

Страница 16: ...air vent 2 Main heat exchanger 3 Detection Electrode 4 C H Flow temperature probe 5 C H Return temperature probe 6 Minimum water pressure switch 7 Siphon 8 Circulation Pump optional for 85 100 115 150...

Страница 17: ...ation is used the room in which the coiler is installedmustbeventilatedusingasuitableairinletwhichcomplies with current legislation In rooms where corrosive vapours may be present for example laundry...

Страница 18: ...xternal wall Type Maximum extension exhaust air m Diameter of pipe mm 45 65 MIN MAX MIN MAX Coaxial system C13 C33 C43 1 12 1 8 80 125 B33 1 12 1 8 80 125 Twin pipe System C13 C23 C33 C43 S1 S2 S1 S2...

Страница 19: ...multiplugs extension leads or adaptors is strictly prohibited It is strictly forbidden to use the piping from the hydraulic heating and gas systems for the appliance earthing connection The boiler is...

Страница 20: ...upply N N FLAME L L BUS T B TA2 SE TNK SOL TA1 CN14 CN13 CN9 1 CN19 CN1 1 1 CN8 1 CN6 1 1 Peripheral unit LV connections HV connections HV connection N N FLAME L L CN19 CN2 CN11 1 1 Gr Detection elect...

Страница 21: ...N18 1 1 Gr Detection electrode Fan Rd Wh LV connection Display C H Return temp probe C H Flow temp probe Minimum water pressure switch Rd Rd Bl Bl Bl Bk CN14 CN3 1 1 CN8 1 CN25 1 Ignitor Diverter valv...

Страница 22: ...N19 CN2 CN11 1 1 Gr Detection electrode Fan CN11 1 LV connection Display C H Return temp probe C H Flow temp probe Minimum water pressure switch Rd Rd Bl Bl Bl Bk CN14 CN3 1 1 CN8 1 CN25 1 Ignitor Div...

Страница 23: ...ures To guarantee safety and the correct operation of the appliance the boiler must be prepared for operation by a qualified technician who possesses the skills which are required by law Electricity s...

Страница 24: ...iler 6 The exhaust duct for combustion products should be suitable and free from any obstructions 7 Any necessary ventilation inlets in the room should be open type B installation 8 Check whether the...

Страница 25: ...ming out of the boiler may be more than 65 C The display will visualise the Chimney Function active at the maximum heating pressure Turn the encoder to select the maximum D H W power Wait for the boil...

Страница 26: ...ion procedure is completed check the CO2 values once again at maximum power If the recorded values fall within the limits indicated in the tables no further calibration is necessary After these operat...

Страница 27: ...gas cock 3 disconnect the electrical connections to the boiler 4 gain access to the combustion chamber as indicated in the paragraph Maintenance Guide General Access 5 add remove the gas diaphragm as...

Страница 28: ...llowing parameters must be set 4 2 1 Activation of temperature adjustment using sensors Select 01 outdoor sensor only 4 2 2 Temperature adjustment curve selection Select the relevant curve according t...

Страница 29: ...omatically but it may be reset by pressing the button Fault 108 Filling Needed ALERT Fault 110 Send Probe Damaged ALERT Call the technical service Fault 501 No flame detected Press the Reset button AL...

Страница 30: ...vation of the anti frost safety device is signalled on the display by the symbol The anti frost device activates only when with the boiler operating correctly the system pressure is correct the boiler...

Страница 31: ...of parameter 2 3 1 Max Adjustable Central Heating Power Proceed as follows 1 Simultaneously press the ESC and buttons for 5 seconds the display will visualise the request for entering the technical co...

Страница 32: ...ct access to the parameters 402 502 602 420 520 620 434 534 634 830 Guided procedures System Filling System air purge Exhaust fumes analysis Service options Service Center Data To insert the name and...

Страница 33: ...ge from 0 to 100 100 RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is changed see Table summarising changes 2 3 3 Minimum power percentage from 0 to 100 100 RESERVED FOR TECHNICAL ASSISTANC...

Страница 34: ...irculation and post ventilation after domestic hot water draw off 2 5 5 Delay start in Central Heating after D H W request from 0 to 30 minutes 0 2 5 7 Anti legionella Function 0 OFF 1 ON 0 Activated...

Страница 35: ...alculate the set point temperature Thermoregulation enabled from 0 to 20 20 If setted 0 the room temperature doesn t influence the calculation of the set point If setted 20 the room temperature has th...

Страница 36: ...0 8 low temperature 0 6 See parameter 422 Only enabled when an outdoor sensor is installed When an outdoor sensor is used the boiler calculates the most suitable delivery temperature taking into accou...

Страница 37: ...to next maintenance from 0 to 60 month 24 If setted the boiler will display that is time to call the installer for maintenance Warning 3P9 Sched Maintanace Call Service ALERT 8 5 1 Enable Maintenance...

Страница 38: ...it forwards d 4 Unhook the two clips on the panel closing off the combustion chamber Pull it forwards and unhook it from the upper pins e Instructions for opening the casing and performing an internal...

Страница 39: ...dded to the water in the heating system in order to avoid the need for repeated draining when this liquid is used make sure it is compatible with the stainless steel used for the bodywork of the boile...

Страница 40: ...try gas category 7 Gas setting 8 Installation type 9 Electrical data 10 Maximum domestic hot water pressure 11 Maximum heating pressure 12 Boiler type 13 NOx class Efficiency 14 Input rating nominal h...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...420010271304 Asistencia T cnica 902 196 547 Ariston Thermo SpA Viale A Merloni 45 60044 Fabriano AN www aristonthermo it info it aristonthermo com...