40
settings - adjustment - problem identifi cation menus
5
2
3
Parallel curve shift
Zone 2 Off set
from - 20 to + 20
0
To adapt the heating curve to the system requirements, shift the curve in parallel so that the calculated fl ow temperature
is modifi ed, in addition to the room temperature.
By accessing this parameter and turning knob
“5” (Figs 1 and 2 - page 4)
, the curve can be shifted in a parallel manner.
The value is indicated on the display, from -20 to +20.
5
2
4
Room sensor Infl uence to calculate the
set-point temperature - Thermoregulation
enabled-
from 0 to 20
20
If setted = 0 the room temperature doesn’t infl uence the calculation of the set-point.
If setted = 20, the room temperature has the maximun infl uence to calculate the set-
point - only active when the BUS device is connected
5
2
5
Maximum Central Heating Temperature Zone2
from 40 to 82 (°C)
82
5
2
6
Minimum Central Heating Temperature Zone 2
from 40 to 82 (°C)
40
5
3
DIAGNOSTICS
display only
5
3
0
Room Temperature Zone 2 - only active when the BUS device is connected
5
3
1
Flow Temperature Zone 2 - only active with MGZ/MCM Kit
5
3
2
Return Temperature Zone 2 - only active with MGZ/MCM Kit
5
3
3
Set Temperature Zone 2 -only active when the BUS device is connected
5
3
4
Heat Request Zone 2
0 = OFF 1 = ON
5
3
4
Pump Status Zone 2
0 = OFF 1 = ON
only active with MGZ/MCM Kit
5
4
ZONE2 DEVICES
5
4
0
Operation Mode Test
0 = OFF
1 = ON
2 = Manual
only active with MGZ/MCM Kit
5
4
1
Valve control
0 = OFF
1 = Open
2 = Closed
5
4
2
Pump control
0 = OFF - 1 = ON
5
5
MULTIZONE
5
5
0
Hydraulic Compensator T
from 0 to 120 (°C)
0
only active with MGZ/MCM Kit
5
5
1
Flow T Off set
from 0 to 40 (°C)
5
7
TEST & UTILITIES
7
0
0
Test Mode
rotate the enoder to select the diff erent test
mode
t -- = Max Heating power
t
--
= Max DHW power (COMBI)
t
--
= Minimum power
t --
Enabled also by pressing for 10 seconds
the Reset button. This function is
deactivated automatically after 10
minutes, or when the E
SC
button is
pressed.
7
0
1
Air purge Function
Press Menu/Ok button to active
8
SERVICE PARAMETERS
8
1
Service code
222
Press +/- to select code 234 and press
M
ENU
/O
K
8
2
BOILER
8
2
0
Modulation Rate
from 0 to 165 MA
8
2
1
Fan Status
0 = OFF 1 = ON
8
2
2
NOT ACTIVE
8
2
3
Pump speed
0= Low speed 1 = High speed
8
2
4
Diverter valve position (COMBI)
0 = D.H.W. 1 =Central Heating
8
2
5
D.H.W. Flow Rate (l/min) (COMBI)
8
2
6
Air Pressure Switch Status
0 = Open 1 = Closed
menu
sub
-menu
par
ameter
Description
range
fac
tor
y
setting