Quick Start Guide: 7500N Series Modular Switches
Cabling the DC Power Supply
Chapter 4: Cabling the Modular Switch
Figure 4-2: Lugs wiring terminations
Figure 4-3: Ground lug wiring termination (PWR-2700W-DC-R)
Note
You can also use a 45
° angled connector instead of the straight connector shown.
Step 2
Use agency-approved compression (pressure) lugs for wiring terminations with a single 5/16"
mounting hole. Two-hole lugs should h
ave 1/4" mounting holes on 5/8" centers.
The PWR-2700W-DC-R ground lug is a right-angle lug. Check the terminations for the
appropriate wire size. Use a ground wire of at least 2 – 4 AWG. Use only copper wire.
Step 3
Slip on heat-shrink tubing on the wire ends before assembling the lugs on to the wire.
•
The lugs must be crimped with the proper tool.
•
The tubing should extend over the lug’s barrel and the wire's insulator.
Step 4
Shrink the tubing with a heat gun.
4.4.3
PWR-3K-DC-RED Power Supply
displays the PWR-3K-DC-RED power supply.
1
Insulated wire
3
-48V + RTN lug
5
1/2”
2
Heat-shrink tubing
4
1/4”
6
5/8”
1
Insulated wire
3
5/16” Ø
2
Ground lug (right angle)
4
Heat-shrink tubing
Содержание 7500N Series
Страница 6: ...vi 9 March 2020Quick Start Guide 7500N Series Modular Switches ...
Страница 54: ...48 Quick Start Guide 7500N Series Modular Switches Power Supply Status Indicators Appendix A Status Indicators ...
Страница 78: ...72 Quick Start Guide 7500N Series Modular Switches Appendix E Line Cards ...
Страница 86: ...80 Quick Start Guide 7500N Series Modular Switches Linecards Appendix F Maintenance and Field Replacement ...
Страница 88: ...82 Quick Start Guide 7500N Series Modular Switches Appendix G Taiwan RoHS Information ...