OVERVIEW
This detector model samples the air in the protected area. An alarm condition is raised when the detected environmental smoke quantity
exceeds the alarm threshold.
COMPATIBILITY
This detector is compatible only with wireless systems based on the Sagittarius protocol.
For more specific information concerning compatibility refer to your fire security system supplier.
INSTALLATION
-
IMPORTANT NOTES
For detector spacing, placement and special applications refer to your specific national standards.
Mount the detector as far as possible from metal objects, metal doors, metal window openings, etc. as well as cable conductors, cables
(especially from computers), otherwise the operating distance may greatly drop. The detector must NOT be installed near electronic devices
and computer equipment that can interfere with its wireless link quality.
This detector must be installed according precisely to the procedures
described in this manual.
Test this detector after installation.
BEFORE INSTALLING THE DETECTOR
1)
Extract the batteries cover from the back of the detector.
2)
Power
-
up the detector removing the isolating tab in the battery
housing. LED indicators signal “Power up”.
3)
Link the detector to the Sagittarius wireless system (
LINKING
).
4)
Check the
WIRELESS LINK QUALITY
.
5)
SELECT A GOOD LOCATION FOR THE DETECTOR
.
6)
Tag device’s loop and address data (
IDENTIFICATION
).
7)
Fix the detector supporting base to the wall (
BASE INSTALLATION
).
LED INDICATORS
Picture 1: provides visual indication for functional conditions and battery levels as indicated in table 1.
ARGUS SECURITY S.R.L.
-
Via del Canneto, 14
-
34015
-
Muggia (TS)
-
Italy
www.argussecurity.it
Table 1
Detector’s status
LEDs indication
Power up
1 second
GREEN
, then 4 X 0.5 second
RED
blink
Linking to the system
Blinking
GREEN
until linking is completed
Link failure
RED
on (continuous)
Normal condition
LEDs off
Alarm
Blinking
RED
: 0.5 second on and 0.5 second off
Battery 1 fault
0.1 second
ORANGE
blink, then 5 seconds off
Battery 2 fault
0.1 second
GREEN
blink, then 5 seconds off
Both batteries fault
0.1 second
ORANGE,
then 5 seconds off
0.1 second
GREEN,
then 5 seconds off
Other fault
sequential
ORANGE
/
GREEN
0.5 second blinking
Tamper
LEDs off
Lost link with wire to
wireless translator /
wireless expander
LEDs off
Test Mode
-
Detector
is more reactive to
aerosol stimulus
Blinking GREEN every 1 second for 1 minute
L
-
OP
-
SG
BI
-
DIRECTIONAL WIRELESS ADDRESSABLE DUAL PATH OPTICAL
SMOKE DETECTOR WITH VARIABLE SENSITIVITY
LED INDICATORS
Picture 1
928k/02