background image

OVERVIEW

 

 

This  detector  model  samples  the  air in the protected  area.  An  alarm  condition is  raised  when  the  detected  environmental  smoke  quantity 

exceeds the alarm threshold.

 

 

COMPATIBILITY

 

 

This detector is compatible only with wireless systems based on the Sagittarius protocol.

 

For more specific information concerning compatibility refer to your fire security system supplier.

 

 

INSTALLATION 

-

 IMPORTANT NOTES

 

 

For detector spacing, placement and special applications refer to your specific national standards.

 

 

Mount  the  detector  as  far  as  possible  from  metal  objects,  metal  doors,  metal  window  openings,  etc.  as  well  as  cable  conductors,  cables 

(especially from computers), otherwise the operating distance may greatly drop. The detector must NOT be installed near electronic devices 

and computer equipment that can interfere with its wireless link quality.

 

 

This detector must be installed according precisely to the procedures 

described in this manual.

 

 

Test this detector after installation.

 

 

BEFORE INSTALLING THE DETECTOR

 

 

1)

 

Extract the batteries cover from the back of the detector.

 

 

2)

 

Power

-

up the detector removing the isolating tab in the battery 

 

     housing. LED indicators signal “Power up”.

 

3)

 

Link the detector to the Sagittarius wireless system (

LINKING

).

 

 

4)

 

Check the 

WIRELESS LINK QUALITY

.

 

 

5)

 

SELECT A GOOD LOCATION FOR THE DETECTOR

.

 

 

6)

 

Tag device’s loop and address data (

IDENTIFICATION

).

 

 

7)

 

Fix the detector supporting base to the wall (

BASE INSTALLATION

).

 

 

LED INDICATORS

 

Picture 1: provides visual indication for functional conditions and battery levels as indicated in table 1.

 

 
 

ARGUS SECURITY S.R.L.

 

-

 Via del Canneto, 14 

-

 34015 

-

 Muggia (TS) 

-

 Italy

 

www.argussecurity.it

 

 

Table 1

 

Detector’s status

 

LEDs indication

 

Power up

 

1 second 

GREEN

, then 4 X 0.5 second 

RED 

blink

 

Linking to the system

 

Blinking 

GREEN 

until linking is completed 

 

Link failure

 

RED 

on (continuous)

 

Normal condition

 

LEDs off

 

Alarm

 

Blinking 

RED

: 0.5 second on and 0.5 second off

 

Battery 1 fault

 

0.1 second 

ORANGE 

blink, then 5 seconds off

 

Battery 2 fault

 

0.1 second 

GREEN

 blink, then 5 seconds off 

 

Both batteries fault

 

0.1 second 

ORANGE,

 then 5 seconds off

 

0.1 second 

GREEN,

 then 5 seconds off

 

Other fault

 

sequential 

ORANGE 

GREEN 

0.5 second blinking

 

Tamper

 

LEDs off

 

Lost link with wire to 

wireless translator / 

wireless expander

 

LEDs off

 

Test Mode 

-

 Detector 

is more reactive to 

aerosol stimulus

 

Blinking GREEN every 1 second for 1 minute

 

L

-

OP

-

SG

 

BI

-

DIRECTIONAL WIRELESS ADDRESSABLE DUAL PATH OPTICAL 

SMOKE DETECTOR WITH VARIABLE SENSITIVITY

 

LED INDICATORS

 

Picture 1

 

928k/02

 

Содержание L-OP-SG

Страница 1: ...ndicators signal Power up 3 Link the detector to the Sagittarius wireless system LINKING 4 Check the WIRELESS LINK QUALITY 5 SELECT A GOOD LOCATION FOR THE DETECTOR 6 Tag device s loop and address data IDENTIFICATION 7 Fix the detector supporting base to the wall BASE INSTALLATION LED INDICATORS Picture 1 provides visual indication for functional conditions and battery levels as indicated in table...

Страница 2: ...nked to translator or expander in this way 1 Move the link switch to the ON position 2 LED indicators will start blinking according to the following table 3 NOTE Ensure the link switch is returned to the BLANK operational position on completion of testing SELECT A GOOD LOCATION FOR THE DETECTOR Choose for the detector a placement position that compliances with your specific standards is reached by...

Страница 3: ...ndicated area picture 7 4 If it works LED indicator will signal Alarm TEST 2 AEROSOL TEST Use only suitable aerosol testers supplied by approved manufacturers 1 Hold a suitable magnet in correspondence of the indicated area picture 7 2 LED indicator will signal Test Mode blinking GREEN every 1 second 3 By following its specific instructions apply the aerosol test device to the detector 4 Wait a fe...

Страница 4: ...ed serviced and maintained on a regular basis to confirm correct operation Smoke detectors may respond differently to various kinds of smoke particles thus application advice should be sought for special risks Detectors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental conditions Refer to and follow national codes of practice...

Отзывы: