p2
The series
DIP 40-
offers a complete range of highly accurate program-
mable digital panel meters. Each instrument is equipped on front face
with a five 14mm high red digits display whose brightness suits applica-
tions in industrial control rooms perfectly.
They allow the display, the checking and transmission of data from any
measurable magnitudes.
• The
DIP 400
(process inputs)
includes in standard:
A DC current or voltage input
Bidirectionnal
±100mV, ±1V, ±10V, ±300V, ±20mA.
- Accuracy: 0.1% of the full scale at +25°C
Thermic drift < 150 ppm/°C
- Measurable scale overstepping from -10% to +10%
-
Scale factor programmable
-
Enlarging effect - Square root extraction
-
Special linearisation on 20 points
-
Supply for 2 or 3 wire sensor 24 V
DC
(±15%) -25 mA
protected from short circuits
• The
DIP 401
(temperature input)
includes as standard:
Either a thermocouple input:
(J, K, N, S, B, W5, T, R, E, W, W3, L)
-
Accuracy: 0.1% of the full scale at +25°C,
or 30µV typical (60µV max.)
-
Thermic drift < 150ppm/°C
CJC efficiency: < 0.03°C/°C ± 0.5°C from -5°C to +55°C
Or a sensor input:
Pt 100
Ω
,
Ni 100
Ω
-
Line resistance influence in 3 wire measure within the class
for 0<Rl<25
Ω
-
Measurement of 2 wire
∆
Pt100 from -200°C to +270°C (0<Rl<10
Ω
)
(R max. 400
Ω
)
-
Max. measure current: 250 µA
-
Accuracy: 0.1% of the full scale at +25°C
-
thermic drift < 150ppm/°C.
1. INTRODUCTION
•
The
DIP 402
(Process, temperature, resistance and
potentiometer inputs)
(See the features of the DIP 400 and DIP 401 on the left hand column)
Resistive sensors
: calibers
0-400
Ω
and 0-2 k
Ω (
0-8 k
Ω
optional)
•
Accuracy: 0.1% for the calibers
0-400
Ω
and 0-8 k
Ω
and
0.5% for the caliber 0-2 k
Ω
(of the full scale at +25°C)
•
Thermic drift < 150ppm/°C
Potentiometers
: from 100
Ω
to 10 k
Ω
•
Accuracy: 0.1% of the full scale at +25°C
•
Thermic drift < 150ppm/°C
AVAILABLE OPTIONS
:
(to be specified on order)
Insulated analog output
: A
Active or passive current, or voltage
Programmable scale ratio with enlarging effect.
Relay output
: R or R4
2 or 4 relays: mode setpoint or mode window.
Recording of the alarms.
Time delay and hysteresis adjustable on each setpoint.
Alarm messages
Insulated digital output
: N
RS 485 2 wire, protocole
MODBUS-JBUS.
Logic input
2 insulated logic inputs with programmable functions
Display hold,
Moving of the decimal point,
Tare function,
zero reset of the min. and max.
Bargraph
: (16 leds display): B
Allows a quick evaluation of the measured value
variations.
Programmable scale factor