Service and Installation Manual
4
INSTALLATION
Location
Units represented in this manual are intended for indoor use only. Be sure the location chosen has a floor
strong enough to support the total weight of the cabinet and contents. A fully loaded unit can weigh as much
as 1500 pounds. For the most efficient refrigeration, be sure to provide good air circulation inside and out.
Inside cabinet:
Do not pack the units so full that air cannot circulate. The refrigerated air is discharged at the top rear of the
unit. It is important to allow for proper air flow from the top rear to the bottom of the unit. Obstructions to this
air flow can cause evaporator coil freeze ups and loss of temperature or overflow of water from the
evaporator drain pan. The shelves have a rear turn up on them to prevent this. However, bags and other
items can still be located to the far rear of the cabinet.
Air is brought into the evaporator coil with fans
mounted to the front of the coil.
Outside cabinet:
Be sure that the unit has access to ample air. Avoid hot corners and locations near stoves and ovens.
It is required that the unit be installed no closer than 3" from any wall including the back with at least
12" of clear space above the unit.
Leveling
A level cabinet looks better and will perform better because the doors will line up with the frames properly.
Use a level to make sure the unit is level from front to back and side to side. If the unit is supplied with
casters, no adjustments are available. Ensure the floor where the unit is to be located is level.
Stabilizing
All models are supplied with casters for your convenience, ease of cleaning underneath and for mobility.
Casters are mounted using 3 bolts in each. It is very important, however, that the cabinet be installed in a
stable condition with the front wheels locked while in use.
Should it become necessary to lay the unit on its side or back for any reason, allow at least 24 hours before
start-up to allow compressor oil to flow back into place. Failure to meet this requirement can cause
compressor failure and unit damage.
Unit repairs will not be subject to standard unit warranties if due to improper installation
procedures.
Electrical connection
Refer to the amperage data on page 3, the serial tag, your local code or the National Electrical Code to be
sure the unit is connected to the proper power source. All models must be on a dedicated 20 amp circuit.
Units using a shared electrical circuit or outlet may not be subject to standard unit warranties.
Use of
extension cords is prohibited and will immediately void the unit warranty.
The unit must be turned OFF and disconnected from the power source whenever
performing service, maintenance functions or cleaning the refrigerated area.
NOTE
DANGER