7.1.7 IEC 103
IEC 103 is the shortened form of the international standard IEC 60870-5-103. The AQ-200 series units
are able to run as a secondary (slave) station. The IEC 103 protocol can be selected for the serial ports
that are available in the device. A primary (master) station can then communicate with the Arcteq
device and receive information by polling from the slave device. The transfer of disturbance recordings
is not supported.
NO
NOTE
TE: Once the configuration file has been loaded, the IEC 103 map of the relay can be found in the
AQtivate software (
Tools
→
IEC 103 map).
The following table presents the setting parameters for the IEC 103 protocol.
Name
Range
Step
Default
Description
Slave address
1…254
1
1
Defines the IEC 103 slave address for the unit.
Measurement interval
0…60 000ms
1ms
2000ms
Defines the interval for the measurements update.
7.1.8 DNP3
DNP3 is a protocol standard which is controlled by the DNP Users Group (www.dnp.org). The
implementation of a DNP3 slave is compliant with the DNP3 subset (level) 2, but it also contains some
functionalities of the higher levels. For detailed information please refer to the DNP3 Device Profile
document (
→
AQ-200 series
→
Resources).
Settings
The following table describes the DNP3 setting parameters.
Table. 7.1.8 - 399. Settings.
Name
Range
Step Default
Description
Enable
DNP3 TCP
0:
Disabled
1:
Enabled
-
0:
Disabled
Enables and disables the DNP3 TCP communication protocol when the
Ethernet port is used for DNP3. If a serial port is used, the DNP3 protocol can
be enabled from
Communication
→
DNP3.
IP port
0…65
535
1
20 000
Defines the IP port used by the protocol.
Slave
address
1…65
519
1
1
Defines the DNP3 slave address of the unit.
Master
address
1…65
534
1
2
Defines the address for the allowed master.
Link layer
time-out
0…60
000ms
1ms
0ms
Defines the length of the time-out for the link layer.
Link layer
retries
1…20
1
1
Defines the number of retries for the link layer.
Diagnostic -
Error counter 0…2
32
-1 1
-
Counts the total number of errors in received and sent messages.
Diagnostic -
Transmitted
messages
0…2
32
-1 1
-
Counts the total number of transmitted messages.
Diagnostic -
Received
messages
0…2
32
-1 1
-
Counts the total number of received messages.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
479