6.2.2.2 DI inputs to excitation
Table. 6.2.2.2 - 369. DI inputs of the excitation unit.
Input name
Description
Increase
Defines the input that increases the reference values of the selected regulator function.
Decrease
Defines the input that decreases the reference values of the selected regulator function.
TestMode
Increase
Defines the input that increases the reference values, if either "ForcedVal" or "OpnLoopRef" is selected
for the "Force PWM control signal" parameter in the "Excitation internal parameters" tab.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
TestMode
Decrease
Defines the input that decreases the reference values, if either "ForcedVal" or "OpnLoopRef" is selected
for the "Force PWM control signal" parameter in the "Excitation internal parameters" tab.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Command AVR
This input is used to enable the AVR control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Command FCR
This input is used to enable the FCR control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Command MVAr
This input is used to enable MVAr control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Command PF
This input is used to enable PF control mode.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Command remote
bus
This input is used to activate the remote bus controls.
See also the parameter "Require permission to remote control" under the "Remote control" tab.
Force IO/params
control only
This input is used to override the process panel or the bus controls by DI controls, if necessary.
Unload Q
See also the parameter "Reactive power unload timeout" under the "MVAR" tab.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Reset
This input is used to reset trips from the excitation application.
Field breaker
status 'Closed in'
This input is used to indicate to the excitation that the field breaker is closed in.
Excitation
OFF command
This input is used to switch the excitation off.
Excitation
ON command
This input is used to switch the excitation on.
Open FB
command
This input is used to open the field breaker.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".
Close FB
command
This input is used to close the field breaker.
This input is read only when the "Control mode" parameter under the "Local control" tab is set to "DI
control".