Input arc point sensor channels
S1, S2, S3, S4 (pressure and light, or light only)
Sensors per channel
3
Performance
Pick-up light intensity
8, 25 or 50 kLx (the sensor is selectable in the order code)
Point sensor detection radius
180 degrees
Start and instant operating time (light only)
Typically <5 ms with dedicated semiconductor outputs (HSO)
Typically <10 ms regular output relays
Table. 9.1.3.3 - 196. High-Speed Outputs (HSO1…2)
Rated values
Rated auxiliary voltage
250 VDC
Continuous carry
2 A
Make and carry 0.5 s
Make and carry 3 s
15 A
6 A
Breaking capacity, DC (L/R = 40 ms)
1 A/110 W
Control rate
5 ms
Operation delay
<1 ms
Polarity
Normally Off
Contact material
Semiconductor
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Table. 9.1.3.3 - 197. Binary input channel
Rated values
Voltage withstand
265 VDC
Nominal voltage
Pick-up threshold
Release threshold
24 VDC
≥
16 VDC
≤
15 VDC
Scanning rate
5 ms
Polarity
Normally Off
Current drain
3 mA
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
NO
NOTE!
TE! Polarity has to be correct.
9.1.3.4 Milliampere module (mA out & mA in)
Table. 9.1.3.4 - 198. Technical data for the milliampere module.
Signals
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
290
© Arcteq Relays Ltd
IM00028
Содержание AQ-T256
Страница 1: ...AQ T256 Transformer protection IED Instruction manual...
Страница 2: ......
Страница 264: ...Figure 7 3 120 Example block scheme A AQ Q T256 T256 Instruction manual Version 2 06 262 Arcteq Relays Ltd IM00028...
Страница 284: ...Figure 8 13 141 Device installation A AQ Q T256 T256 Instruction manual Version 2 06 282 Arcteq Relays Ltd IM00028...