Rated auxiliary voltage
85…265 V (AC/DC)
Power consumption
< 20 W
< 40 W
Maximum permitted interrupt time
< 40 ms with 110 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Other
Minimum recommended fuse rating
MCB C2
Table. 9.1.2.1 - 186. Power supply model B
Rated values
Rated auxiliary voltage
18…72 VDC
Power consumption
< 20 W
< 40 W
Maximum permitted interrupt time
< 40 ms with 24 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Other
Minimum recommended fuse rating
MCB C2
9.1.2.2 CPU communication ports
Table. 9.1.2.2 - 187. Front panel local communication port.
Port
Port media
Copper Ethernet RJ-45
Number of ports
1
Port protocols
PC-protocols
FTP
Telnet
Features
Data transfer rate
100 MB
System integration
Cannot be used for system protocols, only for local programming
Table. 9.1.2.2 - 188. Rear panel system communication port A.
Port
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
286
© Arcteq Relays Ltd