Events
The voltage memory function (abbreviated "M1VT" in event block names) generates events from the
status changes in various activities. The user can select which event messages are stored in the main
event buffer: ON, OFF, or both.
Table. 5.3.27 - 214. Event messages.
Event block name
Event names
M1VT1
Voltage memory enabled
M1VT1
Voltage memory disabled
M1VT1
Voltage low detected ON
M1VT1
Voltage low detected OFF
M1VT1
Current high detected ON
M1VT1
Current high detected OFF
M1VT1
Frequency tracked from CT ON
M1VT1
Frequency tracked from CT OFF
M1VT1
Using Voltage memory ON
M1VT1
Using Voltage memory OFF
M1VT1
Voltage memory blocked ON
M1VT1
Voltage memory blocked OFF
5.4 Control functions
5.4.1 Setting group selection
All relay types support up to eight (8) separate setting groups. The Setting group selection function
block controls the availability and selection of the setting groups. By default, only Setting group 1
(SG1) is active and therefore the selection logic is idle. When more than one setting group is enabled,
the setting group selector logic takes control of the setting group activations based on the logic and
conditions the user has programmed.
The following figure presents a simplified function block diagram of the setting group selection function.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
284
© Arcteq Relays Ltd
IM00020