Table. 5.3.23 - 199. Register content.
Name
Event names
Date and time
dd.mm.yyyy hh:mm:ss.mss
Event
Event name
Time to reach 100 % theta
seconds
Ref. T current
x I
n
Active meas. current
x I
n
T at a given moment
%
Max. temp. rise allowed
degrees
Temp. rise at a given moment
degrees
Hot spot estimate
degrees
Hot spot max. all.
degrees
Trip delay rem.
Remaining time to trip in seconds
Used SG
Setting group 1...8 active
5.3.24 Resistance temperature detectors
Resistance temperature detectors (or RTDs) can be used to measure both temperatures of motors/
generators and ambient temperatures. Typically an RTD is a thermocouple or of type PT100. Up to
three (3) separate RTD modules based on an external Modbus are supported; each can hold up to
eight (8) measurement elements. Up to two (2) separate RTD option cards are supported by this
function. Sixteen (16) individual element monitors can be set for this alarm function, and each of those
can be set to alarm two (2) separate alarms from one selected input. The user can set alarms and
measurements to be either in degrees Celsius or Fahrenheit.
The following figure shows the principal structure of the resistance temperature detection function.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
252
© Arcteq Relays Ltd
IM00020
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...