Event block name
Event names
PWR3
Start ON
PWR3
Start OFF
PWR3
Trip ON
PWR3
Trip OFF
PWR3
Block ON
PWR3
Block OFF
PWR4
Start ON
PWR4
Start OFF
PWR4
Trip ON
PWR4
Trip OFF
PWR4
Block ON
PWR4
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.3.16 - 152. Register content.
Date and time
Event
Pre-trigger
power
Fault power
Pre-fault
power
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
Start/Trip -20ms
power
Start/Trip -20ms
power
Start -200ms
power
0 ms...1800s
Setting group
1...8 active
5.3.17 Motor status monitoring
The motor status monitoring function is designed to be the one place where the user can set up all
necessary motor data and select the used motor protection functions. Settings related to the protection
functions can also be edited inside each function and any changes are updated into this function as
well. In addition to the motor data settings, this function counts the number of times the motor starts,
the number of times the motor start has succeeded, and the number of times the motor has been
stopped. The function also keeps track of the running time and the starting time. Additionally, the
function has a cumulative counter that tells the overall time the motor has been stopped, and it
shows the last time the motor was stopped.
The outputs for the function are the following:
• motor stopped
• motor starting
• motor running
• motor stalled
• missing phase
• load normal
• overloading
• high overcurrent signals.
The signals can be used in indication or in application logics. They are also the basis of the events the
function generates (if so chosen).
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
176
© Arcteq Relays Ltd
IM00020
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...