Instruction manual
–
AQ G3x7 Generator protection IED
195 (211
)
6.7
C
URRENT MEASUREMENT MODULE
Current measurement module is used for measuring current transformer output current.
Module includes three phase current inputs and one zero sequence current input. The
nominal rated current of the input can be selected with a software parameter either 1 A or
5 A.
Table 6-1: Connector allocation of the current measurement module I
•
Number of channels: 4
•
Rated frequency: 50Hz, 60Hz
•
Electronic iron-core flux compensation
•
Low consumption:
≤
0,1 VA at rated current
•
Current measuring range: 35 x In
•
Selectable rated current 1A/5A by parameter
•
Thermal withstand: 20 A (continuously)
o
500 A (for 1 s)
o
1200 A (for 10 ms)
•
Relative accuracy:
±
0,5%
•
Measurement of phase angle: 0.5
º