Instruction manual
–
AQ G3x7 Generator protection IED
183 (211
)
L12 loop X
Reactance of loop L1L2
L23 loop R
Resistance of loop L2L3
L23 loop X
Reactance of loop L2L3
L31 loop R
Resistance of loop L3L1
L31 loop X
Reactance of loop L3L1
Line thermal protection
Calc. Temperature
Calculated line temperature
Synchro check
Voltage Diff
Voltage magnitude difference
Frequency Diff
Frequency difference
Angle Diff
Angle difference
Line measurement (here the displayed information means primary value)
Active Power
–
P
Three-phase active power
Reactive Power
–
Q
Three-phase reactive power
Apparent Power
–
S
Three-phase power based on true RMS voltage and current measurement
Current L1
True RMS value of the current in phase L1
Current L2
True RMS value of the current in phase L2
Current L3
True RMS value of the current in phase L3
Voltage L1
True RMS value of the voltage in phase L1
Voltage L2
True RMS value of the voltage in phase L2
Voltage L3
True RMS value of the voltage in phase L3
Voltage L12
True RMS value of the voltage between phases L1 L2
Voltage L23
True RMS value of the voltage between phases L2 L3
Voltage L31
True RMS value of the voltage between phases L3 L1
Frequency
Frequency
3.3.10
S
TATUS MONITORING THE SWITCHING DEVICES
The status of circuit breakers and the disconnectors (line disconnector, bus disconnector,
earthing switch) are monitored continuously. This function also enables operation of these
devices using the screen of the local LCD. To do this the user can define the user screen
and the active scheme.
3.3.11
T
RIP CIRCUIT SUPERVISION
All four fast acting trip contacts contain build-in trip circuit supervision function. The output
voltage of the circuit is 5V(+-1V). The pickup resistance is 2.5kohm(+-1kohm).
Note: Pay attention to the polarity of the auxiliary voltage supply as outputs are polarity
dependent.