The function block of the current transformer supervision function is shown in figure bellow.
This block shows all binary input and output status signals that are applicable in the AQtivate
300 software.
Figure 3-103: The function block of the current transformer supervision function
The binary input and output status signals of the dead line detection function are listed in
tables below.
Binary status signal
Title
Explanation
CTSuperV_
Blk
_GrO_
Block
Blocking of the function
Table 3-79: The binary input signal of the current transformer supervision function
Binary status signal
Title
Explanation
CTSuperV_
CtFail
_GrI_
CtFail
CT failure signal
Table 3-80: The binary output status signals of the current transformer supervision function
Table 3-81 Setting parameters of the current transformer supervision function
Parameter
Setting value, range
and step
Description
Operation
On
Off
Operating mode selection for the function. Operation can be
either disabled “Off” or
enabled “ON”.
Default setting is enabled.
IPhase Diff
50…90 % by step of
1 %
Phase current difference setting. Default setting is 80 %.
Time delay
100…60000ms
CT supervision time delay. Default setting is 1000ms.