Table. 5.3.10 - 109. Register content.
Date and time
Event
code
Fault
type
Pre-trig
voltage
Fault
voltage
Pre-fault
voltage
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
5696-5895
Descr.
A…A-
B-C
Start average
voltage
Trip -20ms
averages
Start -200ms
averages
0 ms...1800s
Setting
group 1...8
active
5.3.11 Neutral overvoltage protection (U0>; 59N)
The neutral overvoltage function is used for non-directional instant and time-delayed earth fault
protection. Each device with a voltage protection module has four (4) available stages of the
function (U0>, U0>>, U0>>>, U0>>>>). The function constantly measures phase-to-earth voltage
magnitudes and calculates the zero sequence component. Neutral overvoltage protection is scaled
to line-to-line RMS level. When the line-to-line voltage of a system is 100 V in the secondary side, the
earth fault is 100 % of the
U
n
and the calculated zero sequence voltage reaches 100/
√
3 V = 57.74 V.
Below is the formula for symmetric component calculation (and therefore to zero sequence voltage
calculation).
Below are some examples of zero sequence calculation.
Figure. 5.3.11 - 121. Normal situation.
Figure. 5.3.11 - 122. Earth fault in isolated network.
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
171
Содержание AQ-G215
Страница 1: ...AQ G215 Generator protection IED Instruction manual ...
Страница 399: ...Figure 7 4 241 Example block scheme A AQ Q G215 G215 Instruction manual Version 2 04 398 ...
Страница 421: ...Figure 8 14 264 Panel cutout dimensions and device spacing A AQ Q G215 G215 Instruction manual Version 2 04 420 ...
Страница 456: ...10 Ordering information A AQ Q G215 G215 Instruction manual Version 2 04 455 ...