Instruction manual
–
AQ F3x0 Feeder protection IED
157 (162
)
Autoreclosing function, (79)
Operating time inaccuracy
±1% of setti
ng value or
±30ms
Switch on to fault logic
Timer accuracy
±5% or ±15
ms, whichever
is greater
7.4
H
ARDWARE
P
OWER SUPPLY MODULE
Input voltage
80-255VAC
90-300VDC
Nominal voltage
110VDC/220VDC
Maximum interruption
100ms
Maximum power consumption
30W
7.4.1
C
URRENT MEASUREMENT MODULE
Nominal current
1/5A (parameter settable)
0.2A (ordering option)
Number of channels per module
4
Rated frequency
50Hz
60Hz (ordering option)
Burden
<0.1VA at rated current
Thermal withstand
20A (continuous)
500A (for 1s)
1200A (for 10ms)
Current measurement range
0-50xIn
Power consumption at rated
current
0.01
VA with 1A rated current
0.25 VA with 5A rated current
Phase angle accuracy at Ix
≥ 10%
± 1 digit
≤ 0.5 º
Relative accuracy [%]
± 1 digit
± 1
(> 0.5In) with 1A rated current
± 1
(> 0.4In) with 5A rated current
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...