Residual instantaneous overcurrent protection I0>>> (50N)
Operating characteristic
Instantaneous
Picku-up current inaccuracy
<2%
Reset ratio
0.95
Operate time at 2*In
Peak value calculation
Fourier calculation
<15 ms
<25 ms
Reset time
16
–
25 ms
Transient overreach
Peak value calculation
Fourier calculation
80 %
2 %
Residual time overcurrent protection I0>, I0>> (51N)
Pick-up current inaccuracy
< 2%
Operation time inaccuracy
±5% or ±
15ms
Reset ratio
0.95
Minimum operating time with IDMT
35ms
Reset time
Approx 35ms
Transient overreach
2 %
Pickup time
25
–
30ms
7.1.2
D
IRECTIONAL
O
VERCURRENT PROTECTION FUNCTIONS
Three-phase directional overcurrent protection function IDir>, IDir>>
(67)
Pick-up current inaccuracy
< 2%
Operation time inaccuracy
±5% or ±
15ms
Reset ratio
0.95
Minimum operating time with IDMT
35ms
Reset time
Approx 35ms
Transient overreach
2 %
Pickup time
25
–
30ms
Angular inaccuracy
<3°
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...