![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 146](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933146.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
146 (162
)
6.8
C
URRENT MEASUREMENT MODULE
Current measurement module is used for measuring current transformer output current.
Module includes three phase current inputs and one zero sequence current input. The
nominal rated current of the input can be selected with a software parameter either 1 A or
5 A.
Table 6-3: Connector allocation of the current measurement module I
•
Number of channels: 4
•
Rated frequency: 50Hz, 60Hz
•
Electronic iron-core flux compensation
•
Low consumption:
≤
0,1 VA at rated current
•
Current measuring range: 35 x In
•
Selectable rated current 1A/5A by parameter
•
Thermal withstand: 20 A (continuously)
o
500 A (for 1 s)
o
1200 A (for 10 ms)
•
Relative accuracy:
±
0,5%
•
Measurement of phase angle: 0.5
º
, Ix 10 % rated current
No. Name
1 I L1->
2 I L1<-
3 I L2->
4 I L2<-
5 I L3->
6 I L3<-
7 I4->
8 I4<-
"C" CT+/5151
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...