![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 145](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933145.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
145 (162
)
6.7
V
OLTAGE MEASUREMENT MODULE
For voltage related functions (over- /under -voltage, directional functions, distance function,
power functions) or disturbance recorder functionality this module is needed. This module also
has capability for frequency measurement.
For capacitive voltage measurement of the synchrocheck reference, the voltage
measurement module can be ordered with reduced burden in channel VT4. In this module
the burden is < 50 mVA.
The main characteristics of the voltage measurement module:
•
Number of channels: 4
•
Rated frequency: 50Hz, 60Hz
•
Selectable rated voltage (Un): 100/
√
3, 100V, 200/
√
3, 200V by parameter
•
Voltage measuring range: 0.05 Un
–
1.2 Un
•
Continuous voltage withstand: 250 V
•
Power consumption of voltage input:
≤
1 VA at 200V (with special CVT module the burden
is < 50 mVA for VT4 channel)
•
Relative accuracy:
±
0,5 %
•
Frequency measurement range:
±
0,01 % at Ux 25 % of rated voltage
•
Measurement of phase angle: 0.5
º
Ux 25 % of rated voltage
No. Name
1 U L1->
2 U L1<-
3 U L2->
4 U L2<-
5 U L3->
6 U L3<-
7 U Bus->
8 U Bus<-
"D" VT+/2211
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...