![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 144](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933144.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
144 (162
)
6.6
T
RIPPING MODULE
The tripping module applies direct control of a circuit breaker. The module provides fast
operation
and
is
rated
for
heavy
duty
controlling.
The main characteristics of the trip module:
•
4 independent tripping circuits
•
High-speed operation
•
Rated voltage: 110V, 220V DC
•
Continuous carry: 8 A
•
Making capacity: 0.5s, 30 A
•
Breaking capacity: (L/R=40ms) at 220 VDC: 4A
•
Trip circuit supervision for each trip contact
No. Name
1 Trip1 +
2 Trip1 -
3 Trip1 NO
4 Trip 2 +
5 Trip 2 -
6 Trip 2 NO
7 Trip 3 +
8 Trip 3 -
9 Trip 3 NO
10 Trip 4 +
11 Trip 4 -
12 Trip 4 NO
"E" TRIP+/2101