![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 140](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933140.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
140 (162
)
6.2
P
OWER SUPPLY MODULE
The power supply module converts primary AC and/or DC voltage to required system
voltages. Redundant power supply cards extend system availability in case of the outage
of any power source and can be ordered separately if required
Figure 6-1 Connector allocation of the 30W power supply unit
Main features of the power supply module
•
30W input
•
Maximum 100ms power interruption time: measured at nominal input voltage with nominal
power consumption
•
IED system fault contacts (NC and NO): device fault contact and also assignable to user
functions. All the three relay contact points (NO, NC, COM) are accessible to users 80V-
300VDC input range, AC power is also supported
•
Redundant applications which require two independent power supply modules can be
ordered optionally
•
On-board self-supervisory circuits: temperature and voltage monitors
•
Short-circuit-protected outputs
•
Efficiency: >70%
•
Passive heat sink cooling
•
Early power failure indication signals to the CPU the possibility of power outage, thus the
CPU has enough time to save the necessary data to non-volatile memory
No. Name
1 AuxPS+
2 AuxPS-
3 Fault Relay Common
4 Fault Relay NO
5 Fault Relay NC
"A" "B" PS+/1030
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...